Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual
Page 18
Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t
■
1 8
■
Attribute #
Access
Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of Values
157
Get/Set
Active Displays
USINT
Select which display are
active.
(0) Both displays (default)
(1) Lower display only
(2) Upper display only
158
Get/Set
Ramping Mode
USINT
Select when the control set
point ramps to the defined end
set point.
(0) OFF (default)
(1) Ramps on start-up
(2) Ramps on any set
point change
159
Get/Set
Ramp Scale
BOOLEAN
Select the scale of the ramp
rate.
(0) Degrees / hour
(default)
(1) Degrees / minute
160
Get/Set
Ramp Rate
UDINT
Set the rate for the set point
ramp.
0 to 9999 (* 1000)
(default = 100)
161
Get/Set
Lockout
USINT
Set the security level for the
user interface.
(0) No Lockout (default)
(1) Set Point,
Auto/Manual, Alarms, only
(2) Set Point,
Auto/Manual, only
(3) Set Point only
(4) Full Lockout
162
Get/Set
Alarm Acknowledge 1
BOOLEAN
Alarm acknowledge for output 1.
(0) No
(1) Yes
163
Get/Set
Alarm Acknowledge 2
BOOLEAN
Alarm acknowledge for output 2.
(0) No
(1) Yes
164
Get/Set
AC Line Frequency
BOOLEAN
Sets the frequency of the
applied AC line source
(0) - 60 (default)
(1) - 50
165
Get/Set
Profile Type
BOOLEAN
Sets the profile ramp to time
based or rate based
(0) - time based (default)
(1) - ramp based
166
Get/Set
Profile Start
BOOLEAN
Selects where the profile
begins the starting set point,
current static set point or
process temperature.
(0) - set point (default)
(1) - process
167
Get/Set
Guaranteed Soak
Deviation Enable
BOOLEAN
Enables the guaranteed
soak deviation function in
profiles
(0) - disabled (default)
(1) - enabled
168
Get/Set
Guaranteed Soak
Deviation Value
UDINT
Sets the value of deviation
allowed
1 to 999 (*1000)
(default = 1)
169
Get/Set
Process Scale Low mV
UDINT
Set the low scale for process
input
0.00 to 50.00 mV
(*1000) (when Sensor
Type set to mV, default
= 0.00 mV)