Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual
Page 13

Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t
■
1 3
■
Table 23. Setup Object Class Attributes
Table 24. Setup Object Instance Attributes
Attribute #
Access
Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of
Values
100
Get/Set
Sensor Type
USINT
Analog input sensor type
(0)
Thermocouple
(default)
(1)
RTD
(2)
MA
(3)
VOLT
101
Get/Set
Thermocouple
Linearization
USINT
Thermocouple Type
(0)
J
(1)
K (default)
(2)
T
(3)
E
(4)
N
(5)
C
(6)
D
(7)
PTII
(8)
R
(9)
S
(10)
B
102
Get/Set
Temperature Units
USINT
Temperature Units
(0)
°F
(1)
°C (default)
103
Get/Set
Temperature Decimal
Places
USINT
Thermocouple/RTD precision
(0)
0 (default)
(1)
0.0
104
Get/Set
Process Decimal
Places
USINT
Process precision
(0)
0 (default)
(1)
0.0
(2)
0.00
(3)
0.000
105
Get/Set
InfoSense
TM
USINT
Enables the sensor feature, which syn-
chronizes the controller with a Watlow
sensor
(0)
NO (default)
(1)
YES
106
Get/Set
InfoSense
TM
1
UINT
Set sensor point 1 code
0 to 999
(default is 500)
107
Get/Set
InfoSense
TM
2
UINT
Set sensor point 2 code
0 to 999
(default is 500)
108
Get/Set
InfoSense
TM
3
UINT
Set sensor point 3 code
0 to 999
(default is 500)
Attribute #
Access
Rule
Name
DeviceNet Data
Type
Description of
Attribute
Semantics of Values
1
Get
Revision
UINT
Revision of this object
The revision level of
this object (currently 1)
2
Get
Max Instance
UINT
Max allowed
Instances of this
object
1 for this Class