Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual
Series sd6 pid with devicenet, Ordering information and model numbers, Keys and display
0600-0041-0015
Rev D June 2005
Series SD6 PID with DeviceNet
(Addendum)
Watlow’s Series SD6 with DeviceNet offers excellent con-
trol and application flexibility in a 1/16th DIN panel
mount package.
The Series SD6 with DeviceNet has successfully passed
the rigorous testing requirements of ODVA and is also
SEMI-SIG compliant.
This single-channel controller includes a universal sensor
input with two outputs that can be configured as heat,
cool, or alarm. The DeviceNet communications interface is
supplied with either of two standard connectors, a closed
style M12 (Semi-SIG compliant) or an open style connec-
tor.
The Series SD6 with DeviceNet is only available
with one or two outputs.
Ordering Information and
Model Numbers
Control Type
C = PID Control
L = Limit Control
R = Ramping
Power Supply
H = 100 to 240V
Å (ac)
L = 24 V
‡ (ac/dc)
Output 1
C = Switched dc
K = SSR, Form A, 0.5 A
F = Universal process
J = Mechanical relay, Form A, 2 A
Output 2
A = None
C = Switched dc
K = SSR, Form A, 0.5 A
J = Mechanical relay, Form A, 2 A
DeviceNet Communications
N = Open style connector
S = Closed style M12 connector (Semi-SIG compliant)
Display Colors and Custom Options
RG = Red Green
RR = Red Red
XX = Custom options, special overlays, etc.
S D 6 _ _
_ _ _ _ _ _ A - D _ _ _ _ _ _
Table 1. Module Status (MOD) Indicator Light
Table 2. Network Status (NET) Indicator Light
Indicator Light
Description
Off
The device is not online.
The device has not completed the dupli-
cate MAC ID test yet.
The device may not be powered. Look at
Table 1, Module Status Indicator Light.
Green
The device is online and has connections
in the established state.
For a Group 2 Only device it means that
the device is allocated to a Master.
Red
Failed communication device.
The device has detected an error that has
rendered it incapable of communicating on
the network (duplicate MAC ID or Bus-off).
Flashing Green
The device is online, but no connection
has been allocated or an explicit connec-
tion has timed out.
Flashing Red
A poll connection has timed out.
Indicator Light
Description
Off
No power is applied to the device.
Flashing Green-Red
The device is performing a self-test.
Flashing Red
The controller is in Auto mode and an input
error condition
[Er;in] exists. This indication
does not occur if the controller is in the
Manual mode when an input error occurs.
Red
A checksum error
[Er;CS] has occurred.
Green
The device is operating normally.
This document is available as an Adobe Acrobat PDF file at
www.watlow.com; search on “SD6 DeviceNet”.
Advance Key
Advances the lower display
through parameter prompts.
Infinity Key
Returns to the
Home Page.
Up and
Down Keys
In the Home
Page, adjusts
the set point.
In other pages,
changes the
upper display
to a higher or
lower value.
Diagnostic Indicator Lights
Provide operating and diagnostic information about
the module (MOD) and network (NET).
SD6C-XXXA-DXXX shown.
Keys and Display