Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual
Page 15
Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t
■
1 5
■
Attribute #
Access Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of Values
121
Get/Set
Set Point High Limit mA
and volts
DINT
Set the high range for the
set point
Set Point Low Limit +
0.001 to 9999, if Input
Type = mA or Volt (default
= 9999)
(* 1000)
122
Get/Set
Input Filter
USINT
Select filtering action
(1) OFF (no filtering,
default)
(1) Filter display only
(2) Filter control input only
(3) Filter both
123
Get/Set
Filter Value
UDINT
Set the input filter value, units
in seconds
0.0 to 60.0 (default = 0.0)
seconds (* 1000)
124
Get/Set
Output 1 Function
USINT
Set the output 1 function
(0) OFF
(1) Process Alarm
(2) Deviation Alarm
(3) Heat Control (default)
(4) Cool Control
125
Get/Set
Control Method 1
USINT
Set the output 1 control type
Only used with PID control
(1) Fixed Timed Base
(default)
(1) Variable Time Base
126
Get/Set
Fixed Time Base 1
USINT
Set the time base for fixed
time based control
1.0 to 60.0 if Output 1 is a
mechanical relay
0.1 to 60.0 if Output 1 is
not a mechanical relay
Defaults:
20.0 mechanical relay
5.0 solid-state relay
1.0 switched DC
127
Get/Set
Power Limit 1
UINT
Set the maximum power out-
put for a control output
0.0 to 100%
(default = 100%)
128
Get/Set
Output Power Scale Low 1
USINT
Set the low end of the range
within which the output will
scale
0 to 100%
(default = 0)
129
Get/Set
Output Power Scale High 1
USINT
Set the high end of the range
within which the output will
scale
0 to 100%
(default = 100)
130
Get/Set
Output Non-linear Function
1
USINT
Select a non-linear output
curve to match the response
of your system
(0) OFF (default)
(1) Curve 1
(2) Curve 2
131
Get/Set
Analog Output 1 Units
USINT
Set the analog output units
(0) Milliamperes (default)
(1) Volts
132
Get/Set
Analog Output 1 Low Scale
mA
UDINT
Set the low scale for analog
outputs
0.00 to 20.00 mA if output
is set to mA (default =
0.00) (* 1000)