Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual
Page 21
Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t
■
2 1
■
Attribute #
Access
Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of Values
106
Get/Set
Proportional Band Heat
Temperature
UDINT
Set the proportional band for
the heat outputs.
1 to 999°C (x1000), if
Sensor Type is set to
Thermocouple or RTD.
(default = 25°C)
107
Get/Set
Proportional Band Heat
Process
UDINT
Set the proportional band for
the heat outputs.
0.001 to 999.999 units, if
Sensor Type is set to mA
or Volt.
(default = 25.000 units)
108
Get/Set
Integral Heat
UDINT
Set the PID integral in minutes
per repeat for the heat out-
puts.
0.00 to 99.99 (* 1000)
minutes per repeat.
0.00 = disabled
(default = 0.00)
108
Get/Set
Reset Heat
UDINT
Set the PID rate time in min-
utes for the heat outputs.
0.00 to 99.99 (* 1000)
minutes per repeat.
0.00 = disabled
(default = 0.00)
109
Get/Set
Derivative Heat
UDINT
Set the PID derivative time in
minutes for the heat outputs.
0.00 to 9.99
(* 1000) minutes
0.00 = disabled
(default = 0.00)
109
Get/Set
Rate Heat
UDINT
Set the PID rate time in min-
utes for the heat outputs.
0.00 to 9.99 (* 1000)
minutes
0.00 = disabled
(default = 0.00)
110
Get/Set
Dead Band Heat
UDINT
An offset of the heating pro-
portional band from the set
point.
0 to 999 (default = 0)
111
Get/Set
Heat Hysteresis
Temperature
UDINT
Set the control switching hys-
teresis for ON/OFF control.
This determines how far into
the ON region the input needs
to move before the output
actually turns on.
1 to 999 degrees, if
Sensor Type is set to
Thermocouple or RTD
(default = 1.0)
112
Get/Set
Heat Hysteresis Process
UDINT
Set the control switching hys-
teresis for ON/OFF control.
This determines how far into
the ON region the input needs
to move before the output
actually turns on.
0.000 to 999.999 units, if
Sensor Type is set to mA
or Volt.
(default = 1.000)
113
Get/Set
Cool Control Method
USINT
Set the cool control method.
(0) OFF
(1) PID (default)
(2) ON/OFF