Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t

2 1

Attribute #

Access
Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

106

Get/Set

Proportional Band Heat
Temperature

UDINT

Set the proportional band for
the heat outputs.

1 to 999°C (x1000), if
Sensor Type is set to
Thermocouple or RTD.

(default = 25°C)

107

Get/Set

Proportional Band Heat
Process

UDINT

Set the proportional band for
the heat outputs.

0.001 to 999.999 units, if
Sensor Type is set to mA
or Volt.

(default = 25.000 units)

108

Get/Set

Integral Heat

UDINT

Set the PID integral in minutes
per repeat for the heat out-
puts.

0.00 to 99.99 (* 1000)
minutes per repeat.

0.00 = disabled

(default = 0.00)

108

Get/Set

Reset Heat

UDINT

Set the PID rate time in min-
utes for the heat outputs.

0.00 to 99.99 (* 1000)
minutes per repeat.

0.00 = disabled

(default = 0.00)

109

Get/Set

Derivative Heat

UDINT

Set the PID derivative time in
minutes for the heat outputs.

0.00 to 9.99
(* 1000) minutes

0.00 = disabled

(default = 0.00)

109

Get/Set

Rate Heat

UDINT

Set the PID rate time in min-
utes for the heat outputs.

0.00 to 9.99 (* 1000)
minutes

0.00 = disabled

(default = 0.00)

110

Get/Set

Dead Band Heat

UDINT

An offset of the heating pro-
portional band from the set
point.

0 to 999 (default = 0)

111

Get/Set

Heat Hysteresis
Temperature

UDINT

Set the control switching hys-
teresis for ON/OFF control.
This determines how far into
the ON region the input needs
to move before the output
actually turns on.

1 to 999 degrees, if
Sensor Type is set to
Thermocouple or RTD

(default = 1.0)

112

Get/Set

Heat Hysteresis Process

UDINT

Set the control switching hys-
teresis for ON/OFF control.
This determines how far into
the ON region the input needs
to move before the output
actually turns on.

0.000 to 999.999 units, if
Sensor Type is set to mA
or Volt.

(default = 1.000)

113

Get/Set

Cool Control Method

USINT

Set the cool control method.

(0) OFF

(1) PID (default)

(2) ON/OFF