beautypg.com

3 grounding, 3 grounding -28 – Proface APL3000B - Node Box PC User Manual

Page 119

background image

PL3000 Series Hardware Manual

5-28

5.4.3

Grounding

This section describes the precautions for grounding the PL unit.

• When supplying power to the PL unit, be sure to separate the

input/output and power lines, as shown. [diagram (a)]

• If exclusive grounding is not possible, use a common

grounding point. [diagram (b)] A grounding or equivalent

should be used for the grounding point.

Do not use common grounding, since it can lead to an accident or machine breakdown.

• Check that the grounding resistance is

100

Ω or less.

• FG and SG terminals are internally

connected in the PL. When connecting

an external device to the PL using the

SG terminal, be sure to check that no

short-circuit loop is created when you

setup the system.

• The grounding wire should have a cross

sectional area greater than 2mm

2

Create the grounding point as close to

the PL unit as possible, and make the

wire as short as possible. When using a

long grounding wire, replace the thin

wire with a thicker wire, and place it in a

duct.

If the equipment does not function properly

when grounded, disconnect the ground wire

from the FG terminal.

(a) Exclusive Grounding (BEST)

(b) Exclusive Grounding (OK)

(C) Common Grounding (Not OK)

PL

PL

PL

Other

Equipment

Other

Equipment

Other

Equipment