The figure shows the group and the signal names of the terminal blocks:
Connecting the Power Cord
Follow these instructions when supplying power to the unit:
When the frame ground (FG) terminal is connected, verify the wire is grounded. Not
grounding the unit can result in excessive Electromagnetic Interference (EMI).
Grounding is required to meet EMC level immunity.
The shield ground (SG) and FG terminals are connected internally in the unit.
Remove power before wiring to the power terminals of the unit.
The unit uses 24 Vdc power. Using any other level of power can damage both the
power supply and the unit.
Since the unit is not equipped with a power switch, connect a power switch to the unit’s
power supply.
Field wiring terminal marking for wire type (75
° C (167F) copper conductors only).
Pin Arrangement
Group
Pin
Signal
Name
Group
Pin
Signal
Name
Fast
Input/Standard
Input
C1
I0
Fast
Input/Standard
Input
D1
IC0
C2
I1
Standard Input
D2
I2
Standard Input C3
I3
D3
IC1
C4
I5
D4
I4
C5
I7
D5
I6
C6
I9
D6
I8
C7
I11
D7
I10
Temperature
Input
C8
MS0+
Temperature
Input
D8
MS0-
C9
EX0+
D9
EX0-
C10
MS1+
D10
MS1-
C11
EX1+
D11
EX1-
Analog Input
C12
IV0
Analog Input
D12
AIC
C13
IV1
D13
IA0
C14
IA1
Analog Output
D14
AOC
Analog Output
C15
U/I0
D15
U/I1