2 canopen wiring, 2 canopen wiring -7, Line termination – Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 32
![background image](/manuals/358924/32/background.png)
Chapter 3 Installation and Wiring
3-7
3.2.2
CANopen wiring
The CANopen interface uses DSUB 9-pin plug connector. The plug is assigned with the CAN_H, CAN_L and
CAN_GND connections. CAN_H and CAN_L are two physically different bus levels. CAN_GND is the
common reference potential.
Line termination
To minimize the reflections from the end of the cable, a line termination shall be placed close to the 2 ends of
the bus. Connect both ends of the twisted pair cable(CAN_H and CAN_L) to each LT. Use line termination
whose resistance value is 120
Ω. (5%, 1/4 W maximum)
•
The cable’s resistance value should be 70m
Ω/m or less.
•
The above diagrams shows the case used the cable connector “XM2D-0901” by OMRON Co.
GP
Termination
Resistance
Shield
D-sub 9 pin (socket)
CAN-L
Signal
name
2
CAN-H
CAN-GND
FG
Shell
3
7
Pin
GP
D-sub 9 pin (socket)
CAN-L
Signal
name
2
CAN-H
CAN-GND
FG
Shell
3
7
Pin
Shield
Shield
LT = Line Termination
Node 1
Node 2
Node n
LT
CAN_H
CAN_L
CAN_GND
Twisted Pair Cable
LT
Diagram 1
Diagram 2
Diagram 1
Diagram 2
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" LT3200 - 3.8 All-in-One HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"