Curtis PMC 1207/1207A Manual
23
Power Wiring for Series Motor
In every wiring configuration, it is imperative that the field be wired between the
controller’s
B+
and
A2
terminals and that the armature be wired between the
M-
and
A2
terminals. The internal plug diode used in the 1207A is connected
between
M-
and
A2
. Therefore, the armature and field positions cannot be
interchanged. Reversing contactors can be used to switch either the armature or
the field.
Control Wiring for Series Motor
Wiring for the input switches and contactors is shown in Figure 3
A
(see detail
below). The main contactor, if one is used, is normally connected directly to the
controller. Optionally, the main contactor can be switched directly by the
keyswitch or brake, leaving Pin 4 unconnected.
The throttle shown in Figure 3
A
is a 5k
Ω–0 type. Various other throttles can also
be accommodated, and are discussed in the throttle wiring section.
2
A
— INSTALLATION & WIRING: 1207A Controller