Power Wiring for Compound Motor

The field must be wired between

B+

and

A2

and the armature between

M-

and

A2

.

The internal plug diode in the 1207 is connected between

M-

and

A2

; therefore,

the armature and field positions cannot be interchanged.

If the shunt is rated for under 2 amperes, it can be connected directly to the

controller as shown in Figure 4. If the shunt is rated for higher than 2 amperes,
a contactor must be used to control the shunt field.

Control Wiring for Compound Motor

Control wiring for the compound motor application is like that for the standard
(series motor) wiring. The main contactor, if one is used, is normally connected
directly to the controller. Optionally, the main contactor can be switched directly
by the keyswitch or brake, leaving pig Pin 4 unconnected.

The throttle shown in Figure 4 is a 5k

Ω–0 type. Various other throttles can also

be accommodated, and are discussed in the throttle wiring section.

Polarity protection diodes and control fuses must be sized appropriately to

handle the increased current from the shunt field.

2 — INSTALLATION & WIRING: 1207 Controller

16-pin detail (see Fig. 4):

BRAKE

MULTI
MODE

EMERGENCY

REVERSE

FORWARD

REVERSE

KEYSWITCH

EMERGENCY

REVERSE

CHECK

OUTPUT

MAIN

CONTACTOR

FORWARD

CONTACTOR

REVERSE

CONTACTOR

2-WIRE POT

(5 k

Ω)

POT

LOW

8

7

6

5

4

3

2

1

16

15

14

13

12

11

10

9

SHUNT