Curtis PMC 1207/1207A Manual

7

Power Wiring for Series Motor

In every wiring configuration, it is imperative that the field be wired between the
controller’s

B+

and

A2

terminals and that the armature be wired between the

M-

and

A2

terminals. The internal plug diode used in the 1207 is connected between

M-

and

A2

. Therefore, the armature and field positions cannot be interchanged.

Reversing contactors can be used to switch either the armature or the field.

Control Wiring for Series Motor

Wiring for the input switches and contactors is shown in Figure 3 (see detail
below). The main contactor, if one is used, is normally connected directly to the
controller. Optionally, the main contactor can be switched directly by the
keyswitch or brake, leaving Pin 4 unconnected.

The throttle shown in Figure 3 is a 5k

Ω–0 type. Various other throttles can also

be accommodated, and are discussed in the throttle wiring section.

2 — INSTALLATION & WIRING: 1207 Controller

16-pin detail (see Fig. 3):

BRAKE

MULTI
MODE

EMERGENCY

REVERSE

FORWARD

REVERSE

KEYSWITCH

EMERGENCY

REVERSE

CHECK

OUTPUT

MAIN

CONTACTOR

FORWARD

CONTACTOR

REVERSE

CONTACTOR

2-WIRE POT

(5 k

Ω)

POT

LOW

8

7

6

5

4

3

2

1

16

15

14

13

12

11

10

9