Error

No

.

Error Contents/action,

etc.

Alarm reset

619 ABS

unit

encoder
receiving
error

When the simple absolute unit encoder command is issued, the
response could not be properly received.
Cause:
[1] The controller is powered up before the simple absolute unit

when the 24-V power supply is turned on.

[2] The simple absolute unit cannot communicate properly due to

noise, etc. The controller cannot communicate properly with the
simple absolute unit because the communication line in the
encoder cable is disconnected.

Action:
[1] Make sure that the simple absolute unit is powered up before (or

simultaneously with) the controller.

[2] Change the installation location of the controller. Implement noise

measures such as installing a FG, noise filter, clamp filter, etc.
Check the connectors on the encoder relay cable between the
controller and the simple absolute unit for looseness. Or, replace
the cable.

X

Cold-start

level

D12 Encoder

disconnection
error

Encoder signals cannot be detected properly.
Cause:
[1] The connectors on the encoder relay cable are loose or

disconnected.

(When the simple absolute unit is used)
[2] The piano switch 4 on the simple absolute unit is set incorrectly.
[3] The encoder cable model number is incorrect.

(Between the simple absolute unit and the actuator)

Action:
[1] Check the connectors for looseness and disconnection.

The power needs to be turned on again.

(When the simple absolute unit is used)
[2] Check the piano switch setting on the simple absolute unit.
[3] Check the model number of the encoder cable.