beautypg.com

Securitron M34R_Series User Manual

Page 8

background image

PN# 500-13800

Page 8

Rev. D, 04/11

APPENDIX A
Troubleshooting

Problem

Lock Does Not Generate a Magnetic Field

Points of Reference

Check for specified voltage at Magnalock Section

2

Solution

Check for specified current draw at Magnalock

Section 2

Problem

Reduced Holding Force

Points of Reference

Check DC power source is Full-Wave Rectified

(Half-wave Rectifier or AC Power unacceptable)

Section 6.2

Check for specified voltage at Magnalock Section

2

Check for specified current draw at Magnalock

Section 2

Check strike mounting for proper installation

Sections 5.2-5.5

Solution

Check the Magnalock and strike for obstructions

and that contact surfaces are properly cleaned

Section 8

Problem

BondSTAT Does Not Report Secure

Points of Reference

Check for specified voltage at Magnalock Section

2

Check for specified current draw at Magnalock

Section 2

Check strike mounting for proper alignment and

pivoting for proper closure to Magnalock

Table A / Section 5.5.2

Solution

Check the Magnalock and strike for obstructions

and that contact surfaces are properly cleaned

Section 7

Problem

DPS Does Not Report Door Status

Points of Reference

Check strike mounting for proper alignment

Table A / Section 5.5.2

Check for proper door closure Section

7

Check for proper voltage/current on switch

Section 2

Solution

Check resettable protection device

Section 1

Problem

The Magnalock Does Not Release

Points of Reference

Make sure no voltage is present at Magnalock

Section 2

Make sure the Magnalock is not drawing current

Section 2

Check if the strike is sticky and hard to release

Section 7

Solution

Check the Magnalock and strike for obstructions

and that contact surfaces are properly cleaned

Section 7

Problem

The Magnalock is Dirty or Rusty

Points of Reference

Solution

Improper cleaning – Maintenance Equipment

Section 7

Problem

Electronic Noise Interference with

Access Control System

Points of Reference

Solution

Check for voltage from Magnalock to door frame.

There should be no voltage present.

Section 2


IF PROBLEMS PERSIST CALL SECURITRON TOLL FREE

(800) MAG-LOCK

(800) 624-5625