Important – Securitron M34R_Series User Manual
Page 10

PN# 500-13800
Page 10
Rev. D, 04/11
TO SOLVE: INTERSECT ROW (Current) and INTERSECTING COLUMN (Wire Distance)
1.0A
20
Gauge
18
Gauge
16
Gauge
14
Gauge
14
Gauge
12
Gauge
10
Gauge
10
Gauge
8
Gauge
.800A
22
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
12
Gauge
10
Gauge
10
Gauge
8
Gauge
.600A
22
Gauge
20
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
14
Gauge
12
Gauge
10
Gauge
.400A
22
Gauge
22
Gauge
20
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
14
Gauge
12
Gauge
.300A
24
Gauge
22
Gauge
22
Gauge
20
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
14
Gauge
C
U
R
R
E
N
T
.200A
24
Gauge
22
Gauge
22
Gauge
22
Gauge
20
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
50’
[15m]
100’
[30m]
150’
[46m]
200’
[61m]
300’
[91m]
400’
[122m]
500’
[152m]
750’
[229m]
1000’
[305m]
12VDC
WIRE DISTANCE
Table 1
1.0A
22
Gauge
20
Gauge
20
Gauge
18
Gauge
16
Gauge
14
Gauge
14
Gauge
12
Gauge
10
Gauge
.800A
22
Gauge
22
Gauge
20
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
14
Gauge
12
Gauge
.600A
24
Gauge
22
Gauge
22
Gauge
20
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
14
Gauge
.400A
24
Gauge
22
Gauge
22
Gauge
22
Gauge
20
Gauge
18
Gauge
18
Gauge
16
Gauge
14
Gauge
.300A
24
Gauge
24
Gauge
22
Gauge
22
Gauge
22
Gauge
20
Gauge
20
Gauge
18
Gauge
16
Gauge
C
U
R
R
E
N
T
.200A
24
Gauge
24
Gauge
24
Gauge
22
Gauge
22
Gauge
22
Gauge
20
Gauge
20
Gauge
18
Gauge
50’
[15m]
100’
[30m]
150’
[46m]
200’
[61m]
300’
[91m]
400’
[122m]
500’
[152m]
750’
[229m]
1000’
[305m]
24VDC
WIRE DISTANCE
Table 2
The Wire Distance indicated on the table above represents a 2-wire “One-Way” length
from the power supply source to entryway installation area.
The Gauge values specified on the table above represent a 2-wire “Round Trip” length
from the power supply source to entryway installation and returning back to the power
supply source.
IMPORTANT
THE 200’ [61m] WIRE RUN IN EACH TABLE FACTORS A 400’ [122m] ROUND TRIP