3.8 Anti-Pass Back

The programming steps below will allow you to set up and program some basic functions for the anti-pass back feature (APB).
However, you must set up the IN and OUT relay programming table in the Remote Account Manager software. Anti-Pass
Back tables cannot be set from the system keypad. Refer to “Remote account manager for windows” manual 1835-066.

3.8.1 Programming the Anti-Pass Back Mode

Anti-Pass Back (APB) can be set to operate in one of three different modes. PASSIVE APB records an APB Violation and will
allow
entry or exit. ACTIVE APB records an APB Violation and will not allow entry or exit. TRAP APB records an APB Violation
and will allow entry but not exit.

1. Press and enter your four-digit MASTER CODE (beep).

2. Enter for OFF, for PASSIVE, for ACTIVE or for TRAP, then press (beep).

3. Press together to end this programming sequence (beeeeeep).

??

??

??

??

33

DEF

DEF

44

GHI

GHI

00

OPER

OPER

00

OPER

OPER

11

OPER

OPER

22

ABC

ABC

33

DEF

DEF

This programming step is used to allow all cards one ‘move’ either in or out without causing an APB Violation to be recorded.

3.8.2 Re-Sync All Devices

1. Press and enter your four-digit MASTER CODE (beep).

2. Press to Re-Sync ALL devices or press to NOT Re-Sync, then press (beeeeeep).

3. The programming sequence will end itself after all cards have been re-synced.

??

??

??

??

55

JKL

JKL

44

GHI

GHI

11

OPER

OPER

00

OPER

OPER

This programming step is used to re-sync a single card only.

3.8.3 Re-Sync Individual Devices

1. Press and enter your four-digit MASTER CODE (beep).

2. Enter the five-digit device number, then press (beep).

3. Press together to end this programming sequence (beeeeeep).

??

??

??

??

66

MNO

MNO

44

GHI

GHI

00

OPER

OPER

This programming step is used to reset the facility counter. The facility counter keeps track of the number of “IN’s” and
“OUT’s” when using APB mode.

3.8.4 Reset Facility Counter

1. Press and enter your four-digit MASTER CODE (beep).

2. Enter a five-digit number that you want the count to start at, then press (beep).

Example: to start the count at 25, enter 00025.

3. Press together to end this programming sequence (beeeeeep).

??

??

??

??

88

TUV

TUV

44

GHI

GHI

00

OPER

OPER