3.2 DIP-Switch SW 1 and SW 2 Settings

The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on
or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then
turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.

Switch

Function

Setting

Description

SW 2 - Left 4 Switches

2

Spare

4

Exit Loop Port

Output

Typical

Settings

Full Open Input

Factory Set Configuration

Lower Configuration

Warn Before

Operate

1

The output wired to terminal #4 becomes the output from the loop detector
installed in the EXIT loop port. Plug-in loop detector required for “OFF” function.

Normal Setting. Terminal #4 is a normal full open input for a single gate operator.

Reverses Gate

Stops Gate

Switch

Function

Setting

Description

SW 1 - Right 8 Switches

OFF

ON

4-OFF
4-OFF

4-ON
4-ON

5-OFF

5-ON

5-OFF

5-ON

Auto-Close

Timer

Relay Activation

and

LED Indicator

Light Activation

2

1

3

4 and 5

7

8

OFF

ON

OFF

ON

Normal Setting. No sound.
Internal alarm will sound before gate starts and throughout gate’s cycle.

Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.

Self-Test

Gate Opens

Uphill

3

Gate Opens

Downhill

6

Relay activates and LED is ON when the gate is fully open.
Relay activates and LED is ON when the gate is not closed.
Relay activates and LED is ON when the gate is opening and open.
Relay activates and LED is ON when the gate is opening and closing.

Changes the direction
the operator will
open/close the gate.

Opening direction

using ON setting.

Opening direction
using OFF setting.

Opening direction
using ON setting.

Opening direction

using OFF setting.

OFF

ON

Normal Setting. Timer will function normally.
Opening gate will stop and begin to close as soon as all reversing inputs (Reverse
loops, photo sensors) are cleared regardless of the distance the gate has opened.

OFF

ON

Normal Setting. Normal gate operation.

Self-test mode. Operator MUST be disconnected from gate to run self-test.

OFF

ON

Normal Setting. Normal gate operation.

MUST be ON if gate opens UPHILL.

OFF

ON

Normal Setting. Normal gate operation.

MUST be ON if gate opens DOWNHILL.

OFF

Leave in the OFF position.

Left 4 Switches - SW 2

SW 2 is Upside-Down on Circuit Board.

SW 1 - Right 8 Switches

SW 1 is Upside-Down on Circuit Board.

OFF

ON

Normal Setting. Input to terminal #6 and/or reverse loops will REVERSE gate
during CLOSE cycle.

Input to terminal #6 and/or reverse loops will STOP gate during CLOSE cycle.

Quick-Close

Timer Override

Jumper

Wire

Needed