Run has the third highest operating priority. Run ramps to the scaled setpoint speed,
using the Acceleration Time (CP-16). Run can be activated when the MLP–Trim is in
R–Stop or F–Stop, however Run cannot be activated when the MLP–Trim is in Jog.
To activate Run:
• Short the F–Stop and R–Stop inputs to common.
• Open the Jog input.
• Short the Run input to common. (Run is latched and does not need to be
maintained to remain active.)
R-STOP
F-STOP
RUN
JOG
R-STOP
F-STOP
COMMON
JOG
RUN
Close Momentarily
4
5
6
7
8
J6