DeviceNet

11.11 configuration of the safety position of pilot valves

for bus error

If a bus fault occurs, the bus status LED may assume the "Green flashing", "Red flashing" or "Red" status.
(For a description see “Status of the bus LED”, page 55)

The valve safety position and safety module attributes can be used to configure the pilot valve in the event of a bus fault.

If a bus fault occurs, the configuration data of the pilot valves can be accessed acyclically via Explicit Messages.

• The

Get_Attribute_Single service stands for a read access of the configuration data.

• The

Set_Attribute_Single service stands for a write access of the configuration data.

1 data byte for safety mode:
(Attribute address: class 150, instance 1, attri-
butes 7)

1 data byte for valve safety position:
(Attribute address: class 150, instance 1, attributes 6)

Bit

mode

Value assignment

Bit

pilot valve

Value assignment

Bit 0

Character-
istics in event
of bus fault

0 Output safety position
1 Retain last valve

position

Bit 0

Y1
(pilot valve 1)

0 pilot valve 1 OFF
1 pilot valve 1 ON

Bit 1... not used

0 always

Bit
1–7

not used

0 always

Bit 7

Table 19:

Data byte for safety mode

Table 20:

Data byte for valve safety position