Electricalinstallation24VDC

9.3

electrical installation with circular plug-in
connector

Danger!

risk of electric shock.

▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations for electrical equipment.

Connect the control head according to the table.

configuration circular plug (m12 x 1, 8-pole):

6

1

7

5

4

3

2

8

pin

Wire color

4)

Designation

configuration

1

white

limit switch top

IN 1 (= Top)

2

brown

limit switch bottom

IN 2 (= Bot)

3

green

supply voltage

GND

4

yellow

supply voltage +

24 V DC

5

grey

Valve control +

Valve +

6

pink

Valve control –

Valve –

7

-

not used

8

-

not used

Table 3:

Circular plug M12 x 1, 8-pole

The teach function can now be used to automatically determine and read in the end positions of the valve
(description of the teach function see chapter “9.4 Teach function (calibrating the end positions)”).

9.4

Teach function (calibrating the end positions)

The teach function can be used to automatically determine and read in the end positions of the valve.

Danger!

risk of electric shock.

▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations for electrical equipment.

necessary requirements:

Before you can actuate the teach function, you must

• mount the control head on the actuator,

• connect the supply voltage and

• connect the compressed-air supply.