Burkert Type 8691 User Manual
Page 48
48
DeviceNet
Danger!
risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
Procedure:
noTe!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the body casing, do not hold the actuator of the process valve but the
connection housing.
→
Unscrew the body casing (stainless steel) in a counter-clockwise direction.
Body casing
Connection housing
Actuator
Figure 42:
Open control head
→
Set the DIP switches according to the following tables.
Setting the Devicenet address
MAC ID - Medium Access Control Identifier:
[DIP 1=off=0 / DIP 1=on=1 / MAC ID=DIP 1*2
0
+DIP 2*2
1
+ ... +DIP 6*2
5
]
Dip 1
[20=1]
Dip 2
[21=2]
Dip 3
[22=4]
Dip 4
[23=8]
Dip 5
[24=16]
Dip 6
[25=32]
mac iD
off
off
off
off
off
off
0
on
off
off
off
off
off
1
off
on
off
off
off
off
2
...
...
...
...
...
...
...
off
on
on
on
on
on
62
on
on
on
on
on
on
63
Table 15:
Setting the DeviceNet address
english
Type 8691