Electrical data with as-interface bus control, Electrical data with devicenet bus control – Burkert Type 8691 User Manual
Page 15

15
Technicaldata
6.7.2
electrical data with as-interface bus control
Connections
Circular plug-in connector (M12 x 1, 4-pole)
Operating voltage
29.5 V – 31.6 V DC (according to specification)
Outputs
Max. switching capacity
1 W via AS-Interface
Watchdog function
integrated
Devices without external supply voltage:
Max. power consumption
120 mA
Power consumption input during normal operation
(after current reduction;
valve + 1 end position reached)
90 mA
Devices with external supply voltage:
External supply voltage
24 V ± 10 %
The power supply unit must
include a secure disconnection in
accordance with IEC 364-4-41
(PELV or SELV)
Max. power consumption
55 mA (after current reduction ≤ 30 mA)
Max. power consumption from AS-Interface
55 mA
6.7.3
electrical data with Devicenet bus control
Connections
Circular plug-in connector (M12 x 1, 5-pole)
Operating voltage
11 V – 25 V
Max. power consumption
< 80 mA
Output Pull-in current current
≤ 50 mA
Holding current
≤ 30 mA
english
Type 8691