Descriptionofsystem

6.5

pneumatic data

Control medium neutral gases, air, Quality classes in accordance

with DIN ISO 8573-1

Dust content Class 5

max. particle size 40 μm,

max. particle density 10 mg/m

3

Water content Class 3

max. pressure dew point -20 °C or

min. 10 °C below the lowest operating

temperature

Oil content

Class 5

max. 25 mg/m

3

Temperature range

-10 to +50 °C

Pressure range

3 to 7 bar

Air output of pilot valve

250 I

N

/min

(for aeration and deaeration, Q

Nn

-value

according to definition for pressure
drop from 7 to 6 bar absolute)

Connections

Plug-in hose connector ∅6 mm / ¼”
Socket connection G 1/8

6.6

electrical data

Connections:

Cable gland M16 x 1.5, wrench size 22
(clamping area 5 – 10 mm)
with screw terminals
for cable cross-sections 0.14 – 1.5 mm²
Circular plug-in connector M12 x 1, 8-pole

Supply voltage
Pilot valve

24 V DC ± 10 %, residual ripple 10 %

Micro switch

24 V DC max. 2 A

Proximity switches 24 V DC max. 100 mA per proximity switch

Power consumption of pilot valve:

1 W

Position feedback
(option):

1 or 2x Micro switch (24 V DC)
1 or 2x Proximity switch (24 V DC),

normally open PNP

1 or 2x Proximity switch NAMUR (8 V DC)

6.7

Type label (example)

8690 24 V/DC

single act Pilot 0,6

Pmax 7 bar 2 sw.mec.

Tamb 0°C - +55°C

S/N 001000

00185114

D-74653

Ingelfingen

W14UN

ce

Identification number

Supply voltage / Control

Max. operating pressure -
limit switch

Type

Control function - pilot valve

Bar code

Serial number - CE mark

Ambient temperature

Fig. 4: Example of type label

english

Type 8690