2-7

Brooks

®

Model 5850i

Section 2 Installation

Installation and Operation Manual
X-TMF-5850i-MFC-eng
Part Number: 541B108AAG
December, 2008

Chassis Ground

Connect earth ground to pin 14 of the D-connector.

Valve Override (connection optional)

The valve override function allows full opening and closing of the valve
independent of the setpoint:

To open the valve, apply +15 to +28 Vdc to pin 12
To close the valve, connect pin 12 to ground.
Isolating pin 12 (no connection) returns the

controller to normal operation.

NOTE: For normal operation, pin 12 must be left open (floating).

Figure 2-5 Recommended I/O Wiring Configuration for Current Signals (Non-Isolated Power Supply)