beautypg.com

Brooks, Model 5850i – Brooks Instrument 5850i User Manual

Page 15

background image

2-5

Brooks

®

Model 5850i

Section 2 Installation

Installation and Operation Manual
X-TMF-5850i-MFC-eng
Part Number: 541B108AAG
December, 2008

2-7 Electrical Interfacing

To insure proper operation, the 5850i must be connected per Figures 2-2,
2-3 and 2-4 and configured according to Section 2-7. As a minimum, the
following connections must be made for new installations:

Function
Chassis Ground
Signal Output Return
Voltage or Current Signal Output
22.5-28 Vdc Supply
Supply Common
Voltage or Current Setpoint Input
Setpoint Return

Electrical Hook-up

Setpoint (Command) Input

The 5850i Mass Flow Controller can be used with a current (4-20 mAdc)
or voltage (0-5 Vdc) setpoint. To use the current setpoint, connect the
setpoint (+) signal to pin 7 and the setpoint return (-) signal to pin 1 of the
D-connector and configure the PC Board per Section 2-7. To use the
voltage setpoint, connect the setpoint signal to pin 8 and the voltage
setpoint return to pin 1 of the D-connector and configure the PC Board per
Section 2-7.

(The Brook’s MFC acts as a current sink to a setpoint input signal.
The 0/4-20 mA setpoint signal should be “driven” into the MFC input by a
controlled current source. Reference Brook’s device specifications for the
setpoint input impedance.)

Figure 2-3 Maximum Allowable Loop Resistance