Part 1 - transmitter installation, Product identification, General – Dynasonics TFXL Clamp-On Ultrasonic Flow User Manual
Page 8

8
06-TTM-UM-00158 8/2012
Locate the transmitter within the length of transducer cable 
that was supplied with the TFXL system. If this is not possible, 
it is recommended that the cable be exchanged for one that 
is of proper length. Both transducer cables must be of the 
same length.
NOTE: The transducer cable carries low level, high frequency 
signals. In general, it is not recommended to add additional 
cable to the cable supplied with the DTTN, DTTH, DTTS or 
DTTC transducers. If additional cable is required, contact the 
factory to arrange an exchange for a transducer with the 
appropriate length of cable. Cables to 990 feet (300 meters) 
are available. To add cable length to a transducer, the cable 
must be the same type as utilized on the transducer. Twinaxial 
cables can be lengthened with like cable to a maximum 
overall length of 100 feet (30 meters). Coaxial cables can be 
lengthened with RG59 75 Ohm cable and BNC connectors to 
990 feet (300 meters).
If the transmitter will be subjected to a wet environment, it is 
recommended that the cover remain closed after confi gura-
tion is completed. The faceplate of the TFXL is watertight, but 
avoid letting water collect on it. A sealed cord grip or NEMA 
4 conduit connection should be used where cables enter the 
enclosure. Holes not used for cable entry should be sealed 
with plugs. 
To access terminal strips for electronic connectors, loosen 
the four screws in the display lid and remove the cover. The 
terminals where the transducers connect are located under-
neath the display. To connect transducers, remove the four 
screws that secure the display and carefully move it out of 
the way. Do not over stress the ribbon cable located between 
the display and the microprocessor circuit boards.
PRODUCT IDENTIFICATION
The serial number and complete model number of each 
TFXL are located on the side of the instrument enclosure. 
Should technical assistance be required, please provide the 
Customer Service Department
with this information.
PART 1 - TRANSMITTER
INSTALLATION
After unpacking, it is recommended to save the shipping 
carton and packing materials in case the instrument is stored 
or re-shipped. Inspect the equipment and carton for damage. 
If there is evidence of shipping damage, notify the carrier 
immediately.
The enclosure should be mounted in an area that is conve-
nient for servicing, calibration or for observation of the LCD 
readout (if equipped).
1) Locate the transmitter within the length of transducer
cables supplied. If this is not possible, it is recom-
mended that the cable be exchanged for one that is 
of proper length. To add cable length to a transducer, 
the cable must be the same type as utilized on the 
transducer. Twinaxial cables can be lengthened with 
like cable to a maximum overall length of 100 feet (30 
meters). Coaxial cables can be lengthened with RG59 
75 Ohm cable and BNC connectors to 990 feet (300 
meters).
2) Mount the TFXL transmitter in a location:
~ Where little vibration exists.
~ That is protected from corrosive fl uids.
~ That is within the transmitters ambient temperature 
limits -40 to +185° F (-40 to +85° C).
~ That is out of direct sunlight. Direct sunlight may
increase transmitter temperature to above the 
maximum limit.
3) Mounting - Refer to Figure 1.2 for enclosure and
mounting dimension details. Ensure that enough room 
is available to allow for door swing, maintenance and 
conduit entrances. Secure the enclosure to a fl at surface 
with two appropriate fasteners.
4) Conduit Holes - Conduit holes should be used where
cables enter the enclosure. Holes not used for cable 
entry should be sealed with plugs.
NOTE: Use NEMA 4 [IP-65] rated fi ttings/plugs to maintain the 
watertight integrity of the enclosure. Generally, the right side 
conduit hole (viewed from front) is used for power, the bottom 
conduit hole(s) for transducer connections.
2.57
(65.3)
6.66
(169.2)
7.01
(178)
0.875 (22.2) DIA
Conduit Hole
3.17
(80.5)
0.21(5.3) DIA
2 Mounting Holes
FIGURE 1.2 - ENCLOSURE DIMENSIONS
GENERAL
The remote mount TFXL is equipped with three conduit holes 
located in the fl ow meter enclosure that should be suitable 
for most installations. A sealed cord grip or NEMA 4 conduit 
connection should be utilized to retain the NEMA 3 integrity 
of the fl ow meter enclosure. Failure to do so will void the 
manufacturer’s warranty and can lead to product failure. 
The TFXL is housed in an insulating plastic enclosure that 
does not provide continuity of bonding between fi eld wiring 
conduit and the TFXL chassis or other conduits connected to 
the enclosure.
