beautypg.com

Climacool service clearances, The climacool modular chiller - service clearances – ClimaCool IOM AR2 SERIES User Manual

Page 9

background image

7

www.climacoolcorp.com

®

Recommended Clearances

1 . Allow 36” clearance for electrical panels and 24” clearance for rear service access to modules .

2 . Allow a minimum of 18” height clearance for service and 12” for side clearances .

3 . Local building or electrical codes may require additional clearance . Consult applicable codes .

Modular Chiller Bank Dimensions - w/Connnection Flange Gaskets and Blank Off Plates

Model

Dimensions

AR2 Width (ft ./ inches) Depth (inches) Height (w / o panels) Height (w / panels)

25 & 30

50

65

25 & 30

50

65

25 & 30 50

65

25 & 30 50

65

1 module

2’ 7-1/8” 2’11-1/8”

2’11-1/8”

45-5/8”

46-7/8”

46-7/8”

72-7/8” 76-3/4” 76-3/4”

77”

78-3/8” 78-3/8”

2 modules

5’3/4”

5’ 8-3/4”

5’ 8-3/4”

45-5/8”

46-7/8”

46-7/8”

72-7/8” 76-3/4” 76-3/4”

77”

78-3/8” 78-3/8”

3 modules

7’ 6-3/8” 8’ 6-3/8”

8’ 6-3/8”

45-5/8”

46-7/8”

46-7/8”

72-7/8” 76-3/4” 76-3/4”

77”

78-3/8” 78-3/8”

4 modules

10’ 0”

11’4”

11’4”

45-5/8”

46-7/8”

46-7/8”

72-7/8” 76-3/4” 76-3/4”

77”

78-3/8” 78-3/8”

5 modules

12’ 5-5/8” 14’1-5/8” 14’1-5/8”

45-5/8”

46-7/8”

46-7/8”

72-7/8” 76-3/4” 76-3/4”

77”

78-3/8” 78-3/8”

6 modules

15’7/8”

17’7/8”

17’7/8”

45-5/8”

46-7/8”

46-7/8”

72-7/8” 76-3/4” 76-3/4”

77”

78-3/8” 78-3/8”

7 modules

17’ 6-1/2” 19’ 10-1/2” 1 9’10-1/2”

45-5/8”

46-7/8”

46-7/8”

72-7/8” 76-3/4” 76-3/4”

77”

78-3/8” 78-3/8”

NOTES:

1 . Modular chiller bank width dimensions above include (1/8”) between modules, plus (1 -1/2”) for required blank off plate flanges

when piping for a direct return (Refer to Water Piping Configuration - Figure 1) . Example: (5) AR2-65 modules 167-1/2” width +

1-1/2” (Blank off plates) + 5 x 1/8” (flange connection gaskets) = 169-5/8” (14’ 1-5/8”) .

2 . When piping 1 to 5 or more than 5 modules, use reverse return (Refer to Water Piping Configuration - Figure 2) . Example: (7)

AR2-30 modules 206-1/2” width + 1-1/2” (Blank off plates left) + 1-1/2” (Blank off plates right) + 8 x 1/8” (flange connection

gaskets) = 210-1/2” (17’ 6-1/2”) .

ClimaCool Service Clearances