Recommended Clearances
1 . Allow 36” clearance for electrical panels and 24” clearance for rear service access to modules .
2 . Allow a minimum of 18” height clearance for service and 12” for side clearances .
3 . Local building or electrical codes may require additional clearance . Consult applicable codes .
Modular Chiller Bank Dimensions - w/Connnection Flange Gaskets and Blank Off Plates
Model
Dimensions
AR2 Width (ft ./ inches) Depth (inches) Height (w / o panels) Height (w / panels)
25 & 30
50
65
25 & 30
50
65
25 & 30 50
65
25 & 30 50
65
1 module
2’ 7-1/8” 2’11-1/8”
2’11-1/8”
45-5/8”
46-7/8”
46-7/8”
72-7/8” 76-3/4” 76-3/4”
77”
78-3/8” 78-3/8”
2 modules
5’3/4”
5’ 8-3/4”
5’ 8-3/4”
45-5/8”
46-7/8”
46-7/8”
72-7/8” 76-3/4” 76-3/4”
77”
78-3/8” 78-3/8”
3 modules
7’ 6-3/8” 8’ 6-3/8”
8’ 6-3/8”
45-5/8”
46-7/8”
46-7/8”
72-7/8” 76-3/4” 76-3/4”
77”
78-3/8” 78-3/8”
4 modules
10’ 0”
11’4”
11’4”
45-5/8”
46-7/8”
46-7/8”
72-7/8” 76-3/4” 76-3/4”
77”
78-3/8” 78-3/8”
5 modules
12’ 5-5/8” 14’1-5/8” 14’1-5/8”
45-5/8”
46-7/8”
46-7/8”
72-7/8” 76-3/4” 76-3/4”
77”
78-3/8” 78-3/8”
6 modules
15’7/8”
17’7/8”
17’7/8”
45-5/8”
46-7/8”
46-7/8”
72-7/8” 76-3/4” 76-3/4”
77”
78-3/8” 78-3/8”
7 modules
17’ 6-1/2” 19’ 10-1/2” 1 9’10-1/2”
45-5/8”
46-7/8”
46-7/8”
72-7/8” 76-3/4” 76-3/4”
77”
78-3/8” 78-3/8”
NOTES:
1 . Modular chiller bank width dimensions above include (1/8”) between modules, plus (1 -1/2”) for required blank off plate flanges
when piping for a direct return (Refer to Water Piping Configuration - Figure 1) . Example: (5) AR2-65 modules 167-1/2” width +
1-1/2” (Blank off plates) + 5 x 1/8” (flange connection gaskets) = 169-5/8” (14’ 1-5/8”) .
2 . When piping 1 to 5 or more than 5 modules, use reverse return (Refer to Water Piping Configuration - Figure 2) . Example: (7)
AR2-30 modules 206-1/2” width + 1-1/2” (Blank off plates left) + 1-1/2” (Blank off plates right) + 8 x 1/8” (flange connection
gaskets) = 210-1/2” (17’ 6-1/2”) .