beautypg.com

Sequence of operation – ClimaCool IOM AR2 SERIES User Manual

Page 63

background image

61

www.climacoolcorp.com

®

Sequence of Operation

SEQUENCE OF OPERATION

GENERIC INTERFACE - MANUAL ISOLATION

VALVES

Sequence of Operations

Chiller shall be enabled locally or remotely from enable/ disable

contact by BAS via selector switch on face of the “Master Control

Panel” . Pumps for chilled water supply and condenser water supply

shall be started by others . When proof of flow is established in both

the chilled water and condenser water lines, the ClimaCool chiller

shall start . The “Chilled Water Supply” (CHWS) temp . sensor (TS1),

located in the discharge line of respective chiller shall be used to

cycle compressor stages sequentially to maintain setpoint of 45°F

(adjustable from the LCD Display on the Face of the “Master Control

Panel”, or Remotely via either 0-10 VDC or 4-20 ma signal, as

selected . .)

Chillers will be disabled until “Chilled Water Return” (CHWR)

temperature sensor is below 90°F and when the water entering

temperature is above 60°F .

Each module of the chiller has 2 compressors . Stage 1 compressors

shall be started first on lead week and stage 2 compressors shall be

started first on lag weeks to equalize run hours between compressors

1 and 2 of the modules automatically . Compressors shall be staged

with a single compressor per module as required, until all available

modules of the chiller have one compressor running . The remaining

compressors will stage per module, as load requires . Compressors

shall be energized and de-energized by the program, in an order

which will maintain equal run time .

The compressor with most run time will de-energize as the setpoint

is satisfied, and compressor with least run time will energize, as

additional cooling capacity is required .

If a fault is detected the compressor will be disabled and displayed on

the “Master Control Panel” LCD Screen . (Faults must be manually

reset at the chiller) .

The Chiller Status and Run Time in hours for each Compressor

shall be shown on the LCD Display on the “Master Control Panel” .

Common Alarm contact and Chiller Status contact is provided at the

panel .