SAFETY FIRST!
Keep fingers away from valve opening to avoid getting
caught in the moving parts . The electric motor supplies a
sufficient amount of power to cause personal injury . Take
precaution when handling .
Automatic Timer Flush ATF-EA-1 .5 (optional)
Valve Specifications
A . Water-resistant Polypropylene Motor Case
B . High Torque Motors with Perma-lube Gears
C . Open & Close Indicator
D . Stainless Steel Ball Valve & Hardware
E . Auto Reset Circuit Breaker
F . 90 Degree Bidirectional Rotation
G . Controller Case
Fig . 3
TROUBLESHOOTING: If you require further assistance, please call us at (405) 745-3185.
PROBLEM
POSSIBLE CAUSE
SOLUTION
• Valve is leaking past ball
• Seals damaged or worn out
• Install repair kit
• Valve is not stopping at proper
• Adjust limit switches
closed position
• Valve stem leaks
• Worn stem seals
• On metal valves: tighten stem packing
nut 1/2 turn .
CAUTION! Over tightening stem nut
could cause drag on motor and trip
internal circuit breaker. May require
repair kit or new valve.
• Valve body leaks
• Loose body bolts or excessive operating
• Check bolts and observe recommended
pressure
ratings
• Defective seals
• Install repair kits or new valve
• Valve hard to turn
• Swollen seals or product buildup in valve
• Check valve for compatibility with
chamber
product, may require valve cleaning or
new valve
• Valve bolts too tight
• Loosen bolts slightly
• Stem nut too tight
• Loosen stem nut slightly
Automatic Timer Flush Package