beautypg.com

Application parameters – ClimaCool IOM AR2 SERIES User Manual

Page 41

background image

39

www.climacoolcorp.com

®

THE CLIMACOOL MODULAR CHILLER

APPLICATION PARAMETERS

Water Flow Rates

It is imperative that minimum and maximum water flow rates

are not exceeded . Minimum and maximum water flow rates are

defined in the Physical Data tables of this manual . A flow switch

or differential pressure switch is required to confirm flow This

device is supplied by others during initial installation .

Chilled Water Temperature Limits

ClimaCool air-cooled remote modules are designed for a leaving

chilled water temperature range from 42°F to 59°F . All cataloged

modules can operate safely in this range without the need of

special controls or glycol additives . Leaving water temperatures

below 42°F can result in evaporator suction temperatures below

the freezing point of water . Therefore, we recommend a glycol

solution additive that will protect the evaporator from freeze ups

at lower operating suction temperatures .

Water Quality Parameters

Proper care should he given to maintaining a clean system .

Foreign matter such as scale, dirt and corrosion material can

severely affect system performance . Such matter may also cause

blockage which increases water pressure drop and reduces

water flow Due to the regional differences of water conditions,

ClimaCool recommends that a local water treatment specialist

be contacted to determine a proper water treatment program .

ClimaCool does not recommend the use of salt or brackish water

in chilled water systems . Both have a detrimental effect on the

life of system components . ClimaCool modules use a .0001

(ft2-hr oF/Btu) fouling factor for the evaporator in determining

performance ratings . See page 15 for Water Treatment guidelines .

Water Piping Practices

As with any water system, it is important that the system be

clean . If care is taken during installation, the possibility of dirt

related problems are avoided in future operation of the chiller .

The pipe work installer must remove weld scale- rust and

contamination during pipe work fabrication . There are certain

necessary components that should always be installed in the

chilled water loop . (see Water Piping Configurations on page

11 in this manual) Isolation valves are required in the position

shown to isolate the chiller for maintenance . It is also desirable

and a good practice to have valves isolating the pumps .

Refer to the ClimaCool modular chiller water piping

configurations (Figs. I and 2 on page 11) for piping

configurations on multiple modules. Before final piping

connections are made to the chiller, all external water piping

must be thoroughly flushed. Sufficient insulation should be

installed and sealed to prevent condensation and reduce heat

gain. Chilled water volume can be accommodated with the

use of expansion tanks.

Remote Condenser Location

It is vital to select a suitable location for your remote air cooled

condenser in order to allow sufficient air flow into the cavity of

the condenser It is important not to place the condenser into a

“pit”, unless the pit is not any deeper than the condenser height

plus 10 feet, and there is at least a clearance of 2 times the width

of the unit on both sides in between the condenser and the pit

walls . The unit must also be level in relation to the pit opening .

AIR FLOW

1”

Min.

W”

Min.

W”

Min.

Multiple units can be placed next to each other, side by side, as

long as there is at least one width distance between them, that

being the width of the largest unit .

Condensers can be located near fences, as long as there is approx .

50% free area in the fence and the unit is no closer than one

width distance from the fence .

Application Parameters