beautypg.com

Split system interconnecting piping – ClimaCool IOM AR2 SERIES User Manual

Page 51

background image

49

www.climacoolcorp.com

®

Discharge Line Piping Recommendations

All discharge lines should be kept as short as possible, and the

line sizing is determined to provide for a low-pressure drop .

There should always be a gradual negative elevation change

when traversing from the remote condenser location to the

AR2 module section . Avoid any reversing elevation changes

throughout this discharge line run . Horizontal liquid lines should

be sloped downward in the direction of refrigerant flow at a

pitch of 1/8” per foot . The total equivalent distance between

the condenser and the AR2 section (including allowances for

U-bends and 90° elbows) should not exceed 100 feet . Vertical

discharge lines greater than 5 feet require a “P”-trap at the base

of the riser as well as an inverted trap at the top of the discharge

line run (see Figure on page 32) . The inverted trap should be

the highest point in the discharge line . Additional “P”-traps

should be added at every 10 feet of additional vertical rise in the

discharge line . The maximum vertical distance between the lower

AR2 module section and the higher remote condenser location

should be less than 50 feet . AR2 modules equipped with optional

compressor unloading by means of hot gas bypass/combination

liquid injection require the use of double risers for vertical

discharge line runs (see Figure 3 on page 32) .

Remote Condenser Piping Connections

The discharge and liquid line connections at the remote condenser

section are equipped with capped, stub-out tubes . It is mandatory

that isolation ball valves and check valves are field installed at

BOTH the inlet and outlet connection locations of each remote

condenser . These ball valves and check valves are shipped loose

with every ClimaCool AR2 split system chiller package . Refer to

Figures on pages 33 and 34 for schematic representation of the

isolation and check valve functions .

Leak Testing - Refrigeration Side

Prior to startup, the entire system should be leak tested using

electronic leak detection . Carefully leak test both factory and

field made joints including condenser coils . Although each unit is

factory leak tested, joints do loosen and sometimes break during

shipment .

Refrigeration System Reprocessing

Once a refrigeration system has been exposed to atmosphere for

any length of time (several minutes to an hour), it is imperative

that the system undergo a thorough evacuation to remove

moisture and non-condensibles . With split systems, provisions

should be made to evacuate the interconnecting discharge and

liquid lines prior to opening the shutoff valves provided in each

section . Noncondensibles (air, nitrogen trace gases, etc .) trapped

in the system will elevate condensing pressures . This will result

in inefficient system operation and potentially cause nuisance

head pressure trips . Moisture in the system can cause chemical

reactions with many POE oil additives resulting in the formation

of undesirable acids which corrode the system .

IMPORTANT: NEVER start the compressor while in a

vacuum. Serious damage can occur to the motor windings

in this condition. Only use a vacuum pump of known reliable

operation, specifically, one that can achieve a vacuum level of

100-200 microns with the pump service port closed . Prior to

evacuation, make sure all refrigerant isolation valves are OPEN,

and that the main liquid line solenoid valves are energized

(apply 24VAC to the solenoid coils using a 75VA transformer

or equivalent) . Alternatively, you may choose to manifold

multiple evacuation hoses together and connect vacuum lines

to refrigeration access fittings on both sides of the liquid line

solenoid valves . Ensure that the vacuum pump is connected

to both high and low sides of the system with copper tube or

vacuum hoses . A vacuum gauge capable of reading vacuum

levels in microns (with readability as low as 100 microns) must

be connected to the system, preferably close to the compressor

module . Ordinary gauges from a standard charging manifold

are unacceptable! Operate the vacuum pump until a vacuum

level below 500 microns is achieved . Close the vacuum pump

service valves to isolate the pump from the refrigeration system .

This initiates a “vacuum decay test” by monitoring system

pressure rise for a time period of 15 minutes . The refrigeration

system vacuum gauge should not rise more than 200 microns

within this 15 minute period . Pressures that rise beyond this

decay criteria indicate the existence of a leak, or more likely,

indicate the presence of moisture or non-condensibles in the

system . If a leak is suspected, it must be identified and corrected

before proceeding with the evacuation . If moisture contamination

is the suspected problem, rapid evacuation processes may serve

only to freeze the moisture inside the system, allowing only for

the slow process of sublimation to remove all of the water . Then

it is recommended to apply sun lamps to the compressor and

receiver to elevate the temperature inside the system above the

freezing point while evacuating . Successive dry nitrogen fills

and purges can prove equally beneficial in removing excessive

moisture form a system .

Split System Interconnecting Piping