Application Parameters
Performance Multipliers & Pressure Drops
Table AM-6
Performance Adjustment Factors vs. Altitude vs. Chiller Temperature Drop
Chiller
Sea Level
2000 ft.
4000 ft.
6000 ft.
Water Temp.
Capacity Flow, gpm kW Power Capacity Flow, gpm kW Power Capacity Flow, gpm kW Power Capacity Flow, gpm
kW
Drop (
o
F)
Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier
8
0.995
1.246
0.998
0.99
1.244
1.003
0.986
1.238
1.006
0.98
1.232
1.012
10
1.000
1.000
1.000
0.993
0.997
1.004
0.989
0.99
1.007
0.983
0.996
1.014
12
1.005
0.834
1.001
0.996
0.831
1.004
0.992
0.826
1.008
0.986
0.821
1.016
14
1.010
0.716
1.001
0.998
0.714
1.005
0.994
0.709
1.009
0.989
0.704
1.018