ClimaCool Water Piping Configurations
The ClimaCool Modular Chiller -
Water Piping Configurations
Field Piping Direct Return - Optional for 1-5 Modules (Figure 1)
Field Piping Reverse Return (Preferred for 1 to 5 Modules) Required for 6 to 7 Modules (Figure 2)
Unit 1
Unit 2
Unit 3
Unit 5
Unit 4
Blank Off
Plates
60” Sensor Location
(Field-Installed)
PressureTaps
with Shutoff Valves
& Gauges
Flow Out
Flow Switch
Isolation Valve
Thermometer Well
Thermometer Well
PressureTap
w/Shutoff
Valve &
Gauge
Isolation Valves
Strainer
Pump
Flow In
Blank Off
Plate
Blank Off
Plate
60” Sensor Location
(Field-Installed)
7
ti
n
U
3
t
i
n
U
2
t
i
n
U
1
t
i
n
U
Unit 6
Unit 5
Unit 4
Thermometer Well
PressureTap
w/Shutoff
Valve &
Gauge
Isolation Valves
Strainer
Pump
Flow In
Flow Out
Thermometer Well
Flow Switch
Isolation Valves
Pressure Taps
with Shutoff Valves
& Gauges
NOTES:
1 . Figures 1 and 2 are required piping for proper water regulation and distribution through ClimaCool modular chillers .
2 . Module order and incoming/outgoing water flow as shown in both Figure 1 and 2 can be set up as either a left-to-right or right-to-
left configuration .
3 . Condenser Hydronic Circuit shown . Piping configurations are similar for the chilled water hydronic circuit .
4 . For condenser and chilled water (evaporator) inlet/outlet location dimensions, refer to Module Dimensional Data .
5 . A flow switch (supplied by others) is a required safety device for ClimaCool modular chillers on the chilled and condenser water
circuits .
6 . Maximum water flow rates for both evaporator and condenser water header systems in one bank of modules is 1000 GPM . Field
Piping Reverse Return - (Preferred 1 to 5 modules) Required for 6 to 7 Modules (Figure 2)
7 . The chilled water piping on each module is pre-insulated at the factory with ¾” closed cell foam rubber . Insulation (3/4”) on the
chilled water header connection flanges is to be applied in the field by the installer, after the modules are bolted together on site .