Page 119 of 122
0x010C Signal_6_In_Signal_Table_4 Custom Signal 6 (x100)
4 (signed int_32)
0x010E Signal_7_In_Signal_Table_4 Custom Signal 7 (x100)
4 (signed int_32)
0x0110 Signal_8_In_Signal_Table_4 Custom Signal 8 (x100)
4 (signed int_32)
0x0112 Signal_9_In_Signal_Table_4 Custom Signal 9 (x100)
4 (signed int_32)
0x0114 Signal_10_In_Signal_Table_4 Custom
Signal 10 (x100)
4 (signed int_32)
-- --
--
0x0040 * S
Signal_1_In_Signal_Table_S
Read Signal 1 in Signal table S (x100)
4 (signed int_32)
-- --
--
0x0040 * S +
((SS-1) *2)
Signal_SS_In_Signal_Table_S
Read Signal SS in Signal table S (x100)
4 (signed int_32)
-- --
--
0x0182 Signal_1_In_Signal_Table_5 Timer 1
4 (signed int_32)
0x0184 Signal_2_In_Signal_Table_5 Timer 2
4 (signed int_32)
0x0186 Signal_3_In_Signal_Table_5 Timer 3
4 (signed int_32)
0x0188 Signal_4_In_Signal_Table_5 Timer 4
4 (signed int_32)
0x018A Signal_5_In_Signal_Table_5 Timer 5
4 (signed int_32)
0x018C Signal_6_In_Signal_Table_5 Timer 6
4 (signed int_32)
0x018E Signal_7_In_Signal_Table_5 Timer 7
4 (signed int_32)
0x0190 Signal_8_In_Signal_Table_5 Timer 8
4 (signed int_32)
0x0192 Signal_9_In_Signal_Table_5 Timer 9
4 (signed int_32)
0x0194 Signal_10_In_Signal_Table_5 Timer 10
4 (signed int_32)
-- --
--
0x01C2
Signal_1_In_Signal_Table_6
Counter 1
4 (signed int_32)
0x01C4
Signal_2_In_Signal_Table_6
Counter 2
4 (signed int_32)
0x01C6
Signal_3_In_Signal_Table_6
Counter 3
4 (signed int_32)
0x01C8
Signal_4_In_Signal_Table_6
Counter 4
4 (signed int_32)
0x01CA
Signal_5_In_Signal_Table_6
Counter 5
4 (signed int_32)
0x01CC
Signal_6_In_Signal_Table_6
Counter 6
4 (signed int_32)
0x01CE
Signal_7_In_Signal_Table_6
Counter 7
4 (signed int_32)
0x01D0
Signal_8_In_Signal_Table_6
Counter 8
4 (signed int_32)
0x01D2
Signal_9_In_Signal_Table_6
Counter 9
4 (signed int_32)
0x01D4
Signal_10_In_Signal_Table_6
Counter 10
4 (signed int_32)
Table P–CXC Modbus PDU address definition for function code 0x03 (read holding registers)
PDU Address
Variable Name
Variable Description
Response Data Format
0x0001
Relays_Total (Y)
Read number of relays
BINARY
0x0002 Total_Active_Alarms
(Z)
Read total active alarms
BINARY
0x0003
System_Major_Alarm
Read system major alarm status
BINARY
0x0004
System_Minor_Alarm
Read system minor alarm status
BINARY
-- --
--
0x0011
Alarm_Tables_Total (X)
Read number of alarm tables (X<=0x1E)
BINARY
0x0012
Alarms_Total_In_Alarm_Table _1 (A1)
Read number of alarm in alarm table 1
(A1 <= 0x3F)
BINARY
0x0013
Alarms_Total_In_Alarm_Table _2 (A2)
Read number of alarm in alarm table 2
(A2 <= 0x3F)
BINARY
-- --
--
0x0011 + X
Alarms_Total_In_Alarm_Table _X (AX)
Read number of alarm in alarm table X
(AX <= 0x3F)
BINARY
-- --
--
0x0031
Number_of_Active_Alarms_In_Alarm_table _1
Read number of active alarms in alarm table 1
BINARY
0x0032
Number_of_Active_Alarms_In_Alarm_table _2
Read number of active alarms in alarm table 2
BINARY
-- --
0x0031 + (X-1)
Number_of_Active_Alarms_In_Alarm_table _X
Read number of active alarms in alarm table X
BINARY
Table Q–CXC Modbus PDU address definition for function code 0x04 (read input registers)