Submenu Item
Programmable Range
Default Setting
12Vdc
24Vdc
48Vdc
125Vdc
220Vdc
LVD 1
0-9999999999
10.5V
21.00V 42.00V 101.50V
178.50V
LVC 1
0-9999999999
12.5V 25.00V 50.00V 120.83V
212.50V
Alarm Priority
Major/Minor/Message Major
Relay Mapping
1-16 or N/A
(mapping disabled)
1
Control
Check = enable LVD control
Checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD 2
0-9999999999
10.5V
21.00V 42.00V 101.50V
178.50V
LVC 2
0-9999999999
12.5V 25.00V 50.00V 120.83V
212.50V
Alarm Priority
Major/Minor/Message Major
Relay Mapping
1-16 or N/A
(mapping disabled)
2
Control
Check = enable LVD control
Checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD 3
0-9999999999
10.5V
21.00V 42.00V 101.50V
178.50V
LVC 3
0-9999999999
12.5V 25.00V 50.00V 120.83V
212.50V
Alarm Priority
Major/Minor/Message Major
Relay Mapping
1-16 or N/A
(mapping disabled)
3
Control
Check = enable LVD control
Checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD 4-10
0-9999999999
10.5V
21.00V 42.00V 101.50V
178.50V
LVC 4-10
0-9999999999
12.5V 25.00V 50.00V 120.83V
212.50V
Alarm Priority
Major/Minor/Message Major
Relay Mapping
1-16 or N/A
(mapping disabled)
N/A
Control
Check = enable LVD control
Not checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD Inhibit (Status)
Active/Inactive Inactive
Alarm Priority
Major/Minor/Message Major
Relay Mapping
1-16 or N/A
(mapping disabled)
N/A
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
High Volt. Shutdown
0-9999999999
14.25V 29.50V 58.00V 140.17V
246.50V
Alarm Priority
Major/Minor/Message Major
Relay Mapping
1-16 or N/A
(mapping disabled)
N/A
Control
Check = enable LVD control
Not checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
CEMF In-circuit Voltage
0-9999999999
13.70V 27.40V 54.80V 132.43V
232.90V
Bypass Voltage
0-9999999999
13.55V 27.10V 54.20V 130.98V
230.35V
Alarm Priority
Major/Minor/Message Major
Relay Mapping
1-16 or N/A
(mapping disabled)
N/A
Control
Check = enable LVD control
Not checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
Table J–Controls menu defaults