Factory Ranges and Defaults
Submenu Item
Programmable Range
Default Setting
12Vdc
24Vdc
48Vdc
125Vdc
220Vdc
Float (FL) Voltage
0-9999999999
13.50V 27.00V 54.00V 130.50V
229.5V
Equalize (EQ) Voltage
0-9999999999
13.75V 27.50V 55.00V 132.92V
233.75V
Battery Test (BT) Voltage
0-9999999999
11.50V 22.00V 44.00V 106.33V
187.00V
OVP 0-9999999999
14.25V
29.00V 57.00V 137.75V
242.25V
LVA 0-9999999999
11.00V
22.00V 44.00V 106.33V
187.00V
HVA 0-9999999999
14.00V
28.00V 55.50V 134.13V
235.88V
Current Limit (CL)
0-9999999999
100%
Power Limit (PL)
0-9999999999
100%
Equalize Timeout
0-9999999999
30 hours
Battery Test Duration
0-9999999999
8.0 hours
Slope (Adjust)
0-9999999999
1.00%
Backlight Timeout
0-32767
1 minute
Security Code
0-32767
123
Module Start Delay
0-32767
1 second
System Start Delay
0-32767
0 seconds
Soft Start Ramp Rate Normal/Fast
Normal
Temp Display Scale
Celsius/Fahrenheit
Celsius
Current/Power Limit Alarm
Enable/Disable
Disable
Remote Shutdown
Enable/Disable
Enable
Local Access Alarm
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
Power Save
Enable/Disable
Disable
Redundant Rectifiers
0-32767
1
Maximum Power Usage
0-32767
80%
Table E–Rectifiers menu defaults
Submenu Item
Programmable Range
Default Setting
Load Voltage (V1)
Decimal precision: 0-3
2
Load Current (I1)
Decimal precision: 0-3
1
Battery Voltage (V2)
Decimal precision: 0-3
2
Battery Current (I2)
Decimal precision: 0-3
1
AC Mains
Decimal precision: 0-3
1
Battery Temperature
Decimal precision: 0-3
2
Temp Comp Sensor 1
Enable/Disable
Disable
Temp Comp Sensor 2
Enable/Disable
Disable
Temp Comp Sensor 3 (GP1)
Enable/Disable
Disable
Temp Comp Sensor 4 (GP2)
Enable/Disable
Disable
Battery Runtime
Decimal precision: 0-3
2
Battery Capacity
Decimal precision: 0-3
1
Battery Depth of Discharge (DOD)
Decimal precision: 0-3
1
Analog Inputs
See 6.6.1.1
N/A
Digital Inputs (1-8)
High/Low
Low
Rectifier Signals
See Menu Tree
N/A
Custom Signals (1-10)
Decimal precision: 0-3
2
Signal Units (1-10)
A, V, W,
C (F)
V
Table F–Signals menu defaults