Alpha Technologies Cordex Controller Ver.2.0 User Manual
Page 112

Refer to the back of this manual for Factory Service and Technical Support contact information
Alpha Technologies Ltd.
034-136-C0 Rev B WC
Printed in Canada. © 2010 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.
Page 110 of 122
Submenu Item
Programmable Range
Default Setting
12Vdc
24Vdc
48Vdc
125Vdc
220Vdc
Capacity Rating
0-9999999999
0.0 AH
Capacity Calibration
0-9999999999
100%
Open Circuit Voltage
0-9999999999
12.84V 25.68V 51.36V 124.12V
218.28V
Peukert Number
0-9999999999
1.000
Peukert Time 1
0-9999999999
0 hours
Peukert Time 2
0-9999999999
0 hours
Peukert Current 1
0-9999999999
0A
Peukert Current 2
0-9999999999
0A
Temp Comp Slope
0-9999999999
2.50mV/
C
Charge Current Control
Enable/Disable
Disable
Charge Rate Amps
0-9999999999
0.0A
Charge Rate C/X
0-9999999999
0.0
Battery Monitor
Enable/Disable
Disable
Load Type
Power/Current/Resist
Power
Disconnect Voltage
0-9999999999
10.50V 21.00V 42.00V 101.50V
178.50V
Battery Test (BT) End Voltage
0-9999999999
11.63V 22.50V 44.50V 107.54V
189.13V
Periodic Auto BT
Enable/Disable
Disable
Auto BT Interval
1-32767
180 days
Auto Equalize Duration
1-32767
8 hours
Periodic Auto Equalize (EQ)
Enable/Disable
Disable
Auto EQ Interval
1-32767
30 days
(Battery) Charge Auto EQ
Enable/Disable
Enable
Activation Threshold (Auto EQ HV)
0-9999999999
13.25V 26.50V 53.00V 128.08V
225.25V
Arming Threshold (Auto EQ LV)
0-9999999999
12.00V 24.00V 48.00V 116.00V
204.00V
Temp Comp
(Interval fixed at 10 min.)
Enable/Disable Disable
Upper Breakpoint
Voltage 0-9999999999
13.13V 26.25V 52.50V 126.88V
223.13V
Temperature -99999999
to
9999999999
50
C
Lower Breakpoint
Voltage 0-9999999999
13.88V 27.75V 55.50V 134.13V
235.88V
Temperature -99999999
to
9999999999
0
C
Battery Current Termination (BCT) EQ
Enable/Disable
Disable
BCT EQ Duration
0-65536
1 hour
BC Threshold
0.1-999999999
5.0A
Boost (BST) Mode
Enable/Disable
Disable
BST Mode Voltage (V/cell)
0-9999999999 2.30
2.30
2.30
2.30
2.30
BST Mode Timeout
1-32767
4 hours
BST Mode Inhibit
Custom 1 – 20
Custom 1
Table G–Batteries menu defaults
Submenu Item
Programmable Range
24V–48V Defaults
48V–24V Defaults
Output Voltage
0-9999999999
54.00V
27.00V
OVP 0-9999999999
57.00V
28.50V
Input Voltage Shutdown
0-9999999999 21.0V 42.0V
Input Voltage Restart
0-9999999999 25.0V 50.0V
Start Delay
0-32767
1 second
Current Limit (CL) Alarm
Enable/Disable
Enable
Table H–Converters menu defaults