Modbus® Communications Protocol
This feature enables CXC communication of alarms and live signals using Modbus protocol (messaging structure
developed by Modicon®.
A message is encoded in Remote Terminal Unit (RTU) data format and is communicated upon query via
Transmission Control Protocol (TCP) to any Modbus supervisor or master. Reference: Modbus application
protocol specification v1.1a (
www.Modbus-IDA.org
).
The CXC acts as a server on Ethernet networks known as Modbus TCP RTU: TCP/IP over Ethernet, default TCP
port = 502. The server is always up and running when CXC starts up; ready to respond to a client query.
CXC communications cannot be configured as Modbus gateway, to behave as both server and client at the same
time, and does not support Modbus Plus high speed token passing network.
Modbus protocol offers service specified by function codes (see tables provided). A function code is an element of
a Modbus request/reply Protocol Data Unit (PDU). The CXC supports the following:
0x01 (Read Coils): Read CXC relay status bits,
0x02 (Read Discrete inputs): Read alarm tables status bits,
0x03 (Read Holding registers): Read CXC live signals from signals tables,
0x04 (Read Input registers): Read CXC relay or alarm table status registers.
PDU Address
Variable Name
Variable Description
Response Data Format
0x0001
Relay1_Status_Bit
Relay 1 (K1)
BINARY
0x0002
Relay2_Status_Bit
Relay 2 (K2)
BINARY
0x0003
Relay3_Status_Bit
Relay 3 (K3)
BINARY
0x0004
Relay4_Status_Bit
Relay 4 (K4)
BINARY
0x0005
Relay5_Status_Bit
Relay 5 (K5)
BINARY
0x0006
Relay6_Status_Bit
Relay 6 (K6)
BINARY
0x0007
Relay7_Status_Bit
Relay 7 (K7)
BINARY
0x0008
Relay8_Status_Bit
Relay 8 (K8)
BINARY
0x0009
Relay9_Status_Bit
Relay 9 (K9)
BINARY
0x000A
Relay10_Status_Bit
Relay 10 (K10)
BINARY
0x000B
Relay11_Status_Bit
Relay 11 (K11)
BINARY
0x000C
Relay12_Status_Bit
Relay 12 (K12)
BINARY
0x000D
Relay13_Status_Bit
Relay 13 (K13)
BINARY
0x000E
Relay14_Status_Bit
Relay 14 (K14)
BINARY
0x000F Relay15_Status_Bit
Relay 15 (K15)
BINARY
0x0010
Relay16_Status_Bit
Relay 16 (K16)
BINARY
Table N–CXC Modbus PDU address definition for function code 0x01 (read coils)
PDU Address
Variable Name
Variable Description
Response Data Format
0x0001
Alarm1_In_Alarm_Table_1_Status_Bit
Rectifier Fail
BINARY
0x0002 Alarm2_In_Alarm_Table_1_Status_Bit
Rectifier Minor
BINARY
0x0003
Alarm3_In_Alarm_Table_1_Status_Bit
Rect. Major Fail Count
BINARY
0x0004
Alarm4_In_Alarm_Table_1_Status_Bit
Rect. Minor Fail Count
BINARY
0x0005 Alarm5_In_Alarm_Table_1_Status_Bit
Rectifier
Lockout
BINARY
0x0006 Alarm6_In_Alarm_Table_1_Status_Bit Out
Of
Tolerance
BINARY
0x0007
Alarm7_In_Alarm_Table_1_Status_Bit
Rect. Comms Lost
BINARY
0x0008 Alarm8_In_Alarm_Table_1_Status_Bit
Rect. Equalize Activated
BINARY
0x0009
Alarm9_In_Alarm_Table_1_Status_Bit
Rect. AC Mains Fail
BINARY
0x000A Alarm10_In_Alarm_Table_1_Status_Bit
Max Rectifiers Exceeded
BINARY
0x000B
Alarm11_In_Alarm_Table_1_Status_Bit
Fan Fail Alarm
BINARY
0x000C Alarm12_In_Alarm_Table_1_Status_Bit
Power
Save
BINARY
0x000D
Alarm13_In_Alarm_Table_1_Status_Bit
Urgent Rect. AC Mains Fail
BINARY