3 power supply – GE Industrial Solutions 6KCV301DNET User Manual
Page 9
![background image](/manuals/295667/9/background.png)
6KCV301DNET
9
——————
Interface card DeviceNet
——————
4.
The Baud Rate of the SBI card is set via the Switches 7 and 8 of the
Dipswitch S1. The Baud Rate is detected only when the card is switched
on and it can be modified only by switching off and swtching on the card
again.Table 2 shows the relation between the DIP-Switches and the se-
lectable Baud Rate value. The Default value is 125 Kbaud.
Switch 8 Switch 7 Baud Rate
OFF
OFF
125 kBaud
OFF
ON
250 kBaud
ON
OFF
500 kBaud
ON
ON
125 KBaud
DN21
.
5.
The switches 1..6 of the Dip-Switch S1 determine the address.
The address is only detected when the card is switched on. If the address
has been modified, the SBI card has first to be switched off and then on in
order assume the new address.
6.
The Dip-Switch S2 determines the amount of words exchanged over the
Polling I/O. The table describes the relationship between the switches and
the number of Polling I/O words.
switch 4
switch 3
switch 2
switch 1
# of Polling I/O word
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
ON
1
OFF
OFF
ON
OFF
2
OFF
OFF
ON
ON
3
OFF
ON
OFF
OFF
4
OFF
ON
OFF
ON
5
OFF
ON
ON
OFF
6
All
Other
6
tdn0010
Combination
The Polling I/O word number is only detected when the card is switched on. If
the polling I/O word number has been modified, the SBI card has first to be
switched off and then on.
7.
Connect the Bus cable to the BUS terminal.
8.
Switch on the drive.
9.
The LEDS PWR and RUN light up.
10. Switch the Device Net power supply on; the LED H1 lights up.
11. The LED OP lights up when the Master/Slave connection has been established.