Parameter group 14: special functions, Af-60 lp™ micro drive programming guide – GE Industrial Solutions AF-60 LP Micro Drive User Manual
Page 55

4.11. Parameter Group 14: Special Functions
4.11.1. 14-** Special Functions
Parameter group for configuring special frequency converter functions.
4.11.2. Carrier Frequency 14-0*
Parameters for configuring the carrier frequency.
14-01 Motor Noise (Carrier Frequency)
Option:
Function:
Select the carrier frequency in order to minimize e.g. acoustic noise and power loss or maximizing efficiency.
[0]
2 KHz
[1]
*
4 KHz
[2]
8 KHz
[4]
16 KHz
14-03 Overmodulation
Option:
Function:
This feature allows more accurate speed control near and over nominal speed (50/60 Hz). Another advantage with
overmodulation is the ability of staying at a constant speed even though mains is dropping.
[0]
Off
Disables the overmodulation function to avoid torque ripple on the motor shaft.
[1]
*
On
Connects the overmodulation function to obtain an output voltage up to 15% greater than mains voltage.
4.11.3. 14-1* Mains Monitoring
This parameter group supplies functions for handling imbalance on mains.
14-12 Functions at Mains Imbalance
Option:
Function:
Operation under severe mains imbalance conditions reduces drive lift time.
Select function to take place when severe mains imbalance is detected.
[0]
*
Trip
Frequency converter trips.
[1]
Warning
Frequency converter issues a warning.
[2]
Disabled
No action taken.
4.11.4. Trip Reset, 14-2*
Parameters for configuring auto reset handling, special trip handling and control card self test or initialisation.
14-20 Reset Mode
Option:
Function:
Select reset function after tripping. Once reset, frequency converter can be restarted.
[0]
*
Manual Reset
Perform reset via [reset]-button or digital inputs.
[1]
AutoReset 1
Performs one automatic reset after tripping.
[2]
AutoReset 2
Performs two automatic resets after tripping.
[3]
AutoReset 3
Performs three automatic resets after tripping.
[4]
AutoReset 4
Performs four automatic resets after tripping.
[5]
AutoReset 5
Performs five automatic resets after tripping.
AF-60 LP™ Micro Drive Programming Guide