VEGA VEGACOM 557 Siemens 3964 and 3964 R procedure with RK 512 User Manual
Page 30

30
VEGACOM 557 Siemens
S5 functional component
Call up of the Fetch and Receive component for the indicating values
The program reads in the indicating values for the VEGAMET instruments (DISBUS) or
VEGALOG instruments (LOGBUS). The Fetch order was determined in the programming
package COM 525 with order number 1. The statements on the data destination had been
carried out in the programming package with the order determination. Therefore the destina-
tion parameters ZTYP, DBNR, ZANF and ZLAE are negligible when calling up the RECEIVE
component.
FB 1 C:CP524_ST.S5D LAE = 62
Network 1 0000 Output
Name :TEST
:O M 1.1
:ON M 1.1
VKE = 1 force, so that FETCH
:
is worked on in any case
:
:SPA FB 246
enquire FETCH-component
Name :FETCH
SSNR : KY 0,0
Interface no. = 0
A-NR : KY 0,1
Order number = 1
ANZW : MW 10
Indication double word up from MW10
ZTYP : KC DB Data destination (of indication values) in data component
DBNR : KY 0,3
... number 3
ZANF : KF +0
Data destination to DW0
ZLAE : KF +42*
fetch 6 indication values (of 2 signal conditioning instruments
VEGAMET 1 and 2)
PAFE : MB 2
Parametr. failure in MB 2
:
:
:
:
:
:
:
:O M 1.1
:ON M 1.1
VKE = 1 force, so that FETCH
:
is worked on in any case
:
:SPA FB 245
enquire RECEIVE-component
Name :RECEIVE
SSNR : KY 0,0
Interface no. = 0
A-NR : KY 0,0
Order number = 1
ANZW : MW 12
Indication double word up from MW12
ZTYP : KC DB
Data destination in data component
DBNR : KY 0,0
ZANF : KF +0
ZLAE : KF +0
PAFE : MB 3
:
:
:
:
:
:
:BE
*
6DW as offset (see page 23), 6DW for VEGAMET 1, 6DW for VEGAMET 2