VEGACOM 557 Siemens
1
ON
EPG
2
3
4
5
6
7
8
1
ON
EPG
2
3
4
5
6
7
8
1
ON
EPG
2
3
4
5
6
7
8
DIL switch 3 additional board
(negligible)
Switch position (factory setting)
Procedure
Siemens 3964 R
Data transmission
9600 baud
Number of data bits
8
Parity
even
physical interface
RS 232
DIL switch
DIL switch
DIL switch
1
2
3
3.2 Settings on the CP 524
Interface number
The interface number is required in the S5
program for addressing of the communication
processor and can be set with J53. As a
standard feature all bridges are closed (inter-
face number = 0).
CP instrument interface
3 instrument interfaces are available. An
RS 232, a TTY and a RS 422 / 485 interface
module. Depending on the interface used in
the CP, the assignment of the connections on
VEGACOM 557 (see multiple plug) must be
taken into consideration and the setting of the
DIL switches must be made on the
VEGACOM additional board.
Addressing of the process signals
DIL switch 2 additional board
Selection of the baud rate
SW 8
SW 7
SW 6
OFF
OFF
OFF
300 Baud
ON
OFF
OFF
600 Baud
OFF
ON
OFF
1200 Baud
ON
ON
OFF
2400 Baud
OFF
OFF
ON
4800 Baud
ON
OFF
ON
9600 Baud
OFF
ON
ON
19200 Baud
ON
ON
ON
38400 Baud
Number of data bits
SW 5
ON
8 data bits
OFF
7 data bits
Parity
SW 4
SW 3
OFF
OFF
without parity
OFF
ON
without parity
ON
OFF
odd parity (ODD)
ON
ON
even parity (EVEN)
Protocol mode
SW 2
OFF
Siemens 3964
ON
Siemens 3964 R
DCS measured value image
SW 1
OFF
all measured values MET1
all measured values MET2
ON
1 measured value MET 1
1 measured value MET 2