VEGA VEGACOM 557 Siemens 3964 and 3964 R procedure with RK 512 User Manual
Page 29

VEGACOM 557 Siemens
29
S5 functional component
Parameter setting of the RECEIVE component
The information on the data destination, parameter : ZTYP, DBNR, ZANF and ZLAE are irrel-
evant as this information was already defined in the programming package COM 525 with the
order determination.
SSNR:
The interface number corresponds to the switch positions in the CP.
(standard feature = 0)
A-NR:
The order number corresponds to the setting in the programming package COM
525
ANW:
Statement of a double marker word for status description
ZTYP:
KC DB
Data destination is data component
DBNR:
KY 0,0
Data component number, here irrelevant
ZANF:
KF +0
Initial word in DB, here irrelevant
ZLAE:
KF +0
Data length in bytes, here irrelevant
PAFE:
Statement of a marker byte for indication of parameter setting failures
Application example for VEGAMET
Call up in OB20, OB21 and OB22
OB 20
C:CP524_ST.S5D LAE=11
Network 1 0000 Output
:SPA FB 249
Name :SYNCHRON
SSNR : KY 0,0
BLGR : KY 0,3
Block size 64
PAFE : MB 50
Parameter error in merker byte 50
:BE