beautypg.com

Installation guide, H8163-cb – Veris Industries H8163-CB Install User Manual

Page 9

background image

Z202879-0D

PAGE 9

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

03122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

H8163-CB

INSTALLATION GUIDE

Int

Float

R/W NV Model

Description

Notes

41

R/W

Command (bit mapped):
bit 0 (mask 1) = Begin New Demand Sub-Interval
bit 1 (mask 2) = Clear kWh accumulator
bit 2 (mask 4) = Reset Peak Demand
bit 3 (mask 8) = Reset Peak kVAR
bits 4-15 = Write as zeros to avoid activating any additional commands that

might be added in future revisions

42

R/W

NV

Phase Loss, Latching Register (bit mapped):
bit 0: phase A (unpredictable results on phase A)
bit 1: phase B
bit 2: phase C
bits 3 to 15 = write as zeros. This latching register should be cleared by user.

43

R

NV

Count of Phase Losses

The number of times a phase loss has occurred on any phase. This

can never be reset and will roll over from 65535 to zero.

44

R/W

NV

Date/Time Month 1-12 (LSB) Day 1-31 (MSB)

45

R/W

NV

Date/Time Year 0-199 (LSB) Hour 0-23 (MSB)

46

R/W

NV

Date/Time Minutes 0-59 (LSB) Seconds 0-59 (MSB)

47

R

NV

Phase Loss Timestamp, Month 1-12 (LSB) Day 1-31 (MSB)

48

R

NV

Phase Loss Timestamp, Year 0-199 (LSB) Hour 0-23 (MSB)

49

R

NV

Phase Loss Timestamp, Minutes 0-59 (LSB) Seconds 0-59 (MSB)

50

R

NV

Last Restart Timestamp, Month 1-12 (LSB) Day 1-31 (MSB)

51

R

NV

Last Restart Timestamp, Year 0-199 (LSB) Hour 0-23 (MSB)

52

R

NV

Last Restart Timestamp, Minutes 0-59 (LSB) Seconds 0-59 (MSB)

53

R

NV

Last KWh Reset Timestamp, Month 1-12 (LSB) Day 1-31 (MSB)

54

R

NV

Last KWh Reset Timestamp, Year 0-199 (LSB) Hour 0-23 (MSB)

55

R

NV

Last KWh Reset Timestamp, Minutes 0-59 (LSB) Seconds 0-59 (MSB)

56

R

NV

Reset System Firmware Version

57

R

NV

Operating System Firmware Version

58

R

NV

Serial Number LSW

59

R

NV

Serial Number MSW

R: R = Read-only, R/W = read from either format, write to integer format only
NV: Value is stored in non-volatile memory