CP Name

Type

NV Num.

R/W

Applies To

Range

Default Value

Description

INFORMATION
cpMeterModel

SCPTpartNumber

-

R

“Meter” Function

Block

-

-

Meter Manufacturer and Model, stored as an

ASCII string (e.g. “Veris Industries E50F2”).

cpSerialNumber

SCPTserialNumber

-

R

“Meter” Function

Block

-

-

Meter Serial Number.

cpDevMajVer

SCPTdevMajVer

-

R

“NodeObject”

Function Block

-

-

Firmware Major Version (Gateway). See

nvoFullFwRevision for RS, OS firmware

revisions.

cpDevMinVer

SCPTdevMinVer

-

R

“NodeObject”

Function Block

-

-

Firmware Minor Version (Gateway). See

nvoFullFwRevision for RS, OS firmware

revisions.

INSTALLATION DETAILS
cpSystemType

UCPTsystemType

(UCP_Type_3 w/o

resource files)

(SNVT_count ref.)

12

R/W

“Meter” Function

Block

10, 11, 12,

31, 40

40

System Type (see installation instructions for

more detail).

10 Single Phase: A + N
11 Single Phase: A + B
12 Single Split Phase: A + B + N
31 3 Phase Delta, A + B + C, no N
40 3 Phase Wye, A + B + C + N
Note: Only the indicated phases are monitored

for phase loss.

cpDisplayUnits

UCPTdisplayUnits

(UCP_Type_4 w/o

resource files)

(SNVT_count ref.)

13

R/W

“Meter” Function

Block

0, 1

1 (IEEE)

Screen Display Units
0 = IEC (U, V, P, Q, S)
1 = IEEE (VLL, VLN, W, VAR, VA)

cpCtPriRatio

UCPTctPriRatio

(UCP_Type_5 w/o

resource files)

(SNVT_count ref.)

14

R/W

“Meter” Function

Block

5 - 32000(A)

100(A)

CT Ratio – Primary (from CT rating)

cpCtSecRatio

UCPTctSecRatio

(UCP_Type_6 w/o

resource files)

(SNVT_count ref.)

15

R/W

“Meter” Function

Block

1 = 1V
3 = 1/3V

1(V)

CT Ratio – Secondary Interface (1 or 1/3V)

cpPtRatio

UCPTptRatio (UCP_

Type_7 w/o resource

files)

(SNVT_count ref.)

16

R/W

“Meter” Function

Block

1 – 32000

(scaled 0.01-

320.00)

100 (scaled 1:1)

PT Ratio. This value is scaled by 100 (200 = PT

ratio of 2:1). Set to 100 (1.00:1) for no PT.

cpSystemVoltage

UCPTsysVoltage

(UCP_Type_8 w/o

resource files)

(SNVT_count ref.)

17

R/W

“Meter” Function

Block

82 - 32000

(VL-L)

600(VL-L)

System Voltage. This voltage is line to line

unless the system type is 10, where it is line

to neutral. The meter will refuse voltages that

are outside of the range of 82-660 volts when

divided by the PT Ratio (above).

cpPhaseLossVolt

UCPTphLossVolt
(UCP_Type_9 w/o

resource files)

(SNVT_count ref.)

18

R/W

“Meter” Function

Block

1 - 99 (%)

10(%)

Phase Loss Voltage Threshold in percent of

system voltage. Any phase (as configured

by nviSystemType) whose level drops below

this threshold triggers a Phase Loss alert.

For example, with the system type set to 40

(3L+N) and the System voltage set to 480V

L-L, the L-N voltage for each phase should

be 277V. When this threshold is set to 10%,

if any phase drops to less than 10% of 277V

(less than 27.7V), or if any L-L voltage drops

to less than 10% of 480V (less than 48V), the

corresponding phase loss alarm bit in nvoAlert

will be set to 1.