Installation Guide

Power Monitoring

E50F2, E50F5

TM

UI for Setup

Next

Set Current Transducer:

CT V - CT Input Voltage: + or to Select 1.0 or 0.33V.

CT SZ - CT Size: in Amps. Maximum is 32000 Amps.

Set System Configuration:

SYSTM: + or to step through the following System Type options:

System Reg 130 CTs

Description

3L-1n

40 3

Wye Three Phase: A, B, & C with Neutral (Default).

3L 31 3

Delta Three Phase: A, B & C; no Neutral

2L-1n 12

2

Single Split Phase: A & B with Neutral

2L 11 1 Single Phase: A & B; no Neutral

1L-1n 10

1

Single Phase: A to Neutral

System

Type

Current

Transformer

S SYS

Next

S CT

CT V

--------

1.0

.33

CT SZ

--------

100

SYSTM

--------

3L-1n

3L

2L-1n

2L

1L-1n

Bac

k

To

SETU

P

Back

Back

To Setup p. 2 “SPLOS”

Next

S PT

Set Potential Transfomer Ratio:

RATIO – Potential transformer step down is RATIO:1. Default is 1:1

(No PT installed). See Wiring Diagrams section. Set this value before

setting the system voltage to establish the proper range of System

Voltage values.

Potential

Transformer

RATIO

--------

001.00

Back

S V

Back

Sytem

Voltage

Next

Set System Voltage:

V LL – The nominal Line to Line Voltage for the system. This is used

by the meter to calculate the theoretical maximum system power,

and as the reference voltage for setting the Phase Loss threshold.

Maximum is 32000 Volts. For system type 1+N (10), this is a Line to

Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings

that are not within the meter’s operating range when divided by the PT ratio.

V LL

--------

00600

S PWR

Back

Sytem

Voltage

MX KW

--------

103.92

Next

System Power:

MX KW – The theoretical Maximum System Power is calculated by the

meter from the System Voltage, CT size, and System Type. Power Factor

is assumed to be unity. The value of System Power is used to determine

which combinations of pulse weight and duration are valid and will keep up

with the maximum power the meter will see. This value is read only.

Default valurs are in

Bold

To Setup p. 2 “SPASS”