UI for Setup
Next
Set Current Transducer:
CT V - CT Input Voltage: + or – to Select 1.0 or 0.33V.
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Set System Configuration:
SYSTM: + or – to step through the following System Type options:
System Reg 130 CTs
Description
3L-1n
40 3
Wye Three Phase: A, B, & C with Neutral (Default).
3L 31 3
Delta Three Phase: A, B & C; no Neutral
2L-1n 12
2
Single Split Phase: A & B with Neutral
2L 11 1 Single Phase: A & B; no Neutral
1L-1n 10
1
Single Phase: A to Neutral
System
Type
Current
Transformer
S SYS
Next
S CT
CT V
--------
1.0
.33
CT SZ
--------
100
SYSTM
--------
3L-1n
3L
2L-1n
2L
1L-1n
Bac
k
To
SETU
P
Back
Back
To Setup p. 2 “SPLOS”
Next
S PT
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Wiring Diagrams section. Set this value before
setting the system voltage to establish the proper range of System
Voltage values.
Potential
Transformer
RATIO
--------
001.00
Back
S V
Back
Sytem
Voltage
Next
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power,
and as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings
that are not within the meter’s operating range when divided by the PT ratio.
V LL
--------
00600
S PWR
Back
Sytem
Voltage
MX KW
--------
103.92
Next
System Power:
MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power Factor
is assumed to be unity. The value of System Power is used to determine
which combinations of pulse weight and duration are valid and will keep up
with the maximum power the meter will see. This value is read only.
Default valurs are in
Bold
To Setup p. 2 “SPASS”