Veris Industries 196 Manual User Manual

Page 13

background image

24

23

e. Measuring Resistance

WARNING!

Do not attempt to make resistance measurements with
circuit energized. For best results, remove the resistor
completely from the circuit before attempting to measure
it.

NOTE:

To make accurate low ohm measurements, short the ends
of test leads together and record the resistance reading.
Deduct this value from actual readings.

Instrument set-up:

FUNCTION BLACK

RED

MINIMUM

MAXIMUM

TEST LEAD

TEST LEAD

READING

READING

COM

0.01Ω

50.000MΩ

Measurement Procedure:

1. Disconnect power to circuit to be measured.

2. Plug black test lead into the

COM

input jack.

3. Plug red test lead into

input jack.

4. Set the rotary switch to the

function.

5.Connect the test leads to the circuit to be measured.

6. Read the resistance value on the LCD.

d. Measuring AC Amps

CAUTION

Do not attempt to make a current measurement with the
test leads connected in parallel with the circuit to be
tested. Test leads must be connected in series with the
circuit.

WARNING!

Do not attempt to make a current measurement of circuits
with more than 600V present. Instrument damage and/or
personal injury may result
.

Instrument set-up:

FUNCTION BLACK

RED

MINIMUM

MAXIMUM

TEST LEAD

TEST LEAD

READING

READING

COM

mA

0.001mA

500.00mA

COM A 0.0001A

10.000A

Measurement Procedure

:

1. Disconnect power to circuit to be measured.

2. Plug black test lead into the

COM

input jack.

3. Plug the red test into the

mA

or

A

input jack depending

on the value of current to be measured.

4. Set the rotary switch to the

or

function.

5. Press the orange push button.

6. Connect test leads in series to circuit to be measured.

7. Reconnect power to circuit to be measured.

8. Read the current on the LCD.