beautypg.com

York R-410A User Manual

Page 53

background image

251933-YTG-J-1009

Johnson Controls Unitary Products

53

Drive Selection

1.

Determine side or bottom supply air duct application.

2.

Determine desired airflow.

3.

Calculate or measure the amount of external static pressure.

4.

Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear
interpolation may be necessary.)

5.

Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.

6.

Review the BHP compared to the motor options available. Select the appropriate motor and/or drive.

7.

Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.

8.

Determine turns open to obtain the desired operation point.

Example

1.

2200 CFM

2.

1.6 iwg

3.

Using the supply air blower performance table below, the following data point was located: 1478 RPM & 1.82 BHP.

4.

Using the RPM selection table below, Size X and Model Y is found.

5.

1.82 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.

6.

1478 RPM is within the range of the 2 HP drive.

7.

Using the 2 HP motor and drive, 2.5 turns open will achieve 1478 RPM.

Example Supply Air Blower Performance

Air Flow

(CFM)

Available External Static Pressure - IWG

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied

Drive

Standard Drive Option

HIgh Static Drive Option

2000

907

1.00

990

1.07

1070

1.15

1146

1.23

1220

1.31

1291

1.40

1359

1.49

1425

1.58

1488

1.68

1550

1.77

2200

960

1.24

1043

1.31

1123

1.39

1199

1.47

1273

1.55

1344

1.64

1412

1.73

1478

1.82

1541

1.92

1602

2.01

2400

1015

1.51

1099

1.59

1178

1.66

1255

1.74

1329

1.83

1400

1.92

1468

2.01

1534

2.10

1597

2.19

1658

2.29

2600

1074

1.83

1157

1.90

1237

1.98

1314

2.06

1387

2.14

1458

2.23

-

-

-

-

-

-

-

-

Table X: RPM Selection

Size

(Tons)

Model

HP

Max

BHP

Motor

Sheave

Blower

Sheave

5 Turns

Open

4 Turns

Open

3 Turns

Open

2 Turns

Open

1 Turn

Open

Fully

Closed

X

Y

1.5

1.73

1VL44

AK56

930

995

1060

1130

1195

1260

2

2.3

1VP56

AK56

1325

1395

1460

1525

1590

1660