York R-410A User Manual
Page 28

251933-YTG-J-1009
28
Johnson Controls Unitary Products
85°F
95°F
750
77
33.8
2.5
12.4
11.0
9.6
-
-
-
33.9
2.8
11.8
10.4
9.1
-
-
-
72
30.4
2.5
15.0
13.6
12.2
10.7
-
-
29.7
2.8
14.1
12.8
11.4
10.1
-
-
67
27.0
2.5
17.6
16.2
14.7
13.3
11.9
-
25.5
2.8
16.5
15.1
13.8
12.4
11.1
-
62
22.8
2.5
19.1
17.7
16.3
14.9
13.4
12.0
20.8
2.8
17.6
16.2
14.9
13.5
12.2
10.8
900
77
35.7
2.5
13.8
12.1
10.4
-
-
-
35.6
2.8
13.1
11.5
9.9
-
-
-
72
32.1
2.5
16.6
14.9
13.3
11.6
-
-
31.2
2.8
15.7
14.1
12.5
10.9
-
-
67
28.5
2.5
19.4
17.7
16.1
14.4
12.8
-
26.8
2.8
18.2
16.6
15.0
13.5
11.9
-
62
24.0
2.5
21.1
19.4
17.8
16.1
14.4
12.8
21.8
2.8
19.5
17.9
16.3
14.7
13.1
11.5
57
19.7
2.5
19.7
19.7
18.6
17.0
15.3
13.6
17.3
2.7
17.3
17.3
16.1
14.5
12.9
11.3
1050
77
37.5
2.5
15.1
13.2
11.3
-
-
-
37.3
2.8
14.5
12.6
10.8
-
-
-
72
33.7
2.5
18.2
16.3
14.4
12.5
-
-
32.7
2.8
17.2
15.4
13.6
11.7
-
-
67
29.9
2.5
21.2
19.3
17.4
15.5
13.6
-
28.1
2.8
20.0
18.2
16.3
14.5
12.7
-
62
25.2
2.5
23.0
21.1
19.2
17.3
15.4
13.5
22.8
2.8
21.4
19.5
17.7
15.8
14.0
12.2
57
20.7
2.5
20.7
20.7
20.2
18.3
16.4
14.5
18.1
2.7
18.1
18.1
17.5
15.7
13.8
12.0
1200
77
39.4
2.5
16.4
14.3
12.2
-
-
-
39.1
2.8
15.8
13.7
11.6
-
-
-
72
35.4
2.5
19.7
17.6
15.5
13.3
-
-
34.2
2.8
18.8
16.7
14.6
12.5
-
-
67
31.4
2.5
23.0
20.9
18.8
16.6
14.5
-
29.4
2.8
21.8
19.7
17.6
15.5
13.5
-
62
26.5
2.5
25.0
22.9
20.7
18.6
16.4
14.3
23.9
2.8
23.3
21.2
19.1
17.0
14.9
12.8
57
21.7
2.5
21.7
21.7
21.7
19.6
17.4
15.3
18.9
2.7
18.9
18.9
18.9
16.8
14.7
12.6
1350
72
36.6
2.5
20.9
18.6
16.2
13.9
-
-
35.8
2.8
20.1
17.8
15.5
13.2
-
-
67
32.5
2.5
24.3
22.0
19.7
17.4
15.1
-
30.7
2.8
23.3
21.0
18.7
16.4
14.0
-
62
27.4
2.5
26.4
24.1
21.8
19.5
17.1
14.8
25.0
2.7
24.9
22.6
20.2
17.9
15.6
13.3
57
22.5
2.5
22.5
22.5
22.5
20.2
17.8
15.5
19.8
2.7
19.8
19.8
19.8
17.5
15.2
12.8
1500
72
37.9
2.5
22.0
19.5
17.0
14.5
-
-
37.3
2.7
21.5
18.9
16.4
13.8
-
-
67
33.6
2.5
25.6
23.1
20.6
18.2
15.7
-
32.1
2.7
24.8
22.3
19.7
17.2
14.6
-
62
28.4
2.5
27.8
25.3
22.8
20.3
17.8
15.3
26.1
2.7
26.1
23.9
21.4
18.8
16.3
13.7
57
23.2
2.5
23.2
23.2
23.2
20.7
18.3
15.8
20.7
2.7
20.7
20.7
20.7
18.2
15.6
13.1
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR036 (3.0 Ton) Reheat (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65