York R-410A User Manual
Page 26

251933-YTG-J-1009
26
Johnson Controls Unitary Products
115°F
125°F
750
77
35.3
3.5
12.8
10.9
8.0
-
-
-
32.1
3.9
10.5
9.6
6.6
-
-
-
72
32.0
3.5
19.0
16.0
13.1
10.1
-
-
29.2
3.9
17.9
14.8
11.8
8.8
-
-
67
28.8
3.5
25.1
21.1
18.2
15.2
12.3
-
26.2
3.9
24.9
20.0
17.0
14.0
11.0
-
62
26.8
3.5
26.8
26.8
21.7
18.7
15.8
12.9
24.8
3.9
24.8
24.8
20.2
17.2
14.2
11.2
900
77
36.2
3.5
15.8
12.3
8.9
-
-
-
32.8
3.9
14.5
10.9
7.4
-
-
-
72
32.8
3.5
21.4
18.0
14.5
11.0
-
-
29.8
3.9
20.3
16.7
13.2
9.6
-
-
67
29.5
3.5
27.1
23.6
20.2
16.7
13.2
-
26.8
3.9
26.1
22.5
19.0
15.4
11.8
-
62
27.5
3.5
27.5
27.5
24.0
20.6
17.1
13.7
25.3
3.9
25.3
25.3
22.5
19.0
15.4
11.8
57
27.6
3.5
27.6
27.5
24.0
20.6
17.1
13.6
25.6
3.9
25.6
25.4
21.9
18.3
14.8
11.2
1050
77
37.1
3.5
18.7
13.7
9.7
-
-
-
33.5
3.9
18.5
12.3
8.1
-
-
-
72
33.7
3.5
23.9
19.9
15.9
11.9
-
-
30.4
3.9
22.7
18.6
14.5
10.4
-
-
67
30.2
3.5
29.0
26.1
22.1
18.2
14.2
-
27.3
3.9
27.3
25.0
20.9
16.8
12.7
-
62
28.2
3.5
28.2
28.2
26.4
22.4
18.4
14.5
25.8
3.9
25.8
25.8
24.8
20.7
16.6
12.5
57
28.3
3.5
28.3
28.2
26.4
22.4
18.4
14.4
26.1
3.9
26.1
26.0
24.1
20.0
15.9
11.8
1200
77
38.0
3.5
21.7
15.1
10.6
-
-
-
34.1
3.9
22.5
13.6
8.9
-
-
-
72
34.5
3.5
26.3
21.8
17.3
12.8
-
-
31.0
3.9
25.2
20.5
15.9
11.2
-
-
67
31.0
3.5
31.0
28.6
24.1
19.6
15.1
-
27.8
3.9
27.8
27.5
22.8
18.2
13.5
-
62
28.9
3.5
28.9
28.9
28.7
24.2
19.7
15.2
26.3
3.9
26.3
26.3
26.3
22.5
17.8
13.2
57
28.9
3.5
28.9
28.9
28.7
24.2
19.7
15.2
26.6
3.9
26.6
26.6
26.4
21.7
17.1
12.4
1350
72
34.4
3.5
28.4
23.5
18.6
13.6
-
-
30.7
3.9
27.2
22.2
17.1
12.0
-
-
67
30.9
3.5
30.9
29.7
25.8
20.9
15.9
-
27.6
3.9
27.6
27.6
24.5
19.5
14.4
-
62
28.8
3.5
28.8
28.8
28.8
23.8
18.9
14.0
26.2
3.9
26.2
26.2
26.2
21.5
16.4
11.3
57
28.9
3.5
28.9
28.9
28.8
23.9
18.9
14.0
26.4
3.9
26.4
26.4
26.3
21.2
16.1
11.0
1500
72
34.4
3.5
30.5
25.2
19.8
14.4
-
-
30.5
3.8
29.3
23.8
18.3
12.8
-
-
67
30.9
3.5
30.9
30.9
27.5
22.1
16.8
-
27.4
3.8
27.4
27.4
26.3
20.7
15.2
-
62
28.8
3.5
28.8
28.8
28.8
23.4
18.1
12.7
26.0
3.9
26.0
26.0
26.0
20.5
14.9
9.4
57
28.9
3.5
28.9
28.9
28.9
23.5
18.1
12.8
26.2
3.9
26.2
26.2
26.2
20.7
15.2
9.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR036 (3.0 Ton) Cooling (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65