Zr036-060 bottom duct application, Zr036 (3 ton belt drive) bottom duct, Zr048 (4 ton belt drive) bottom duct – York R-410A User Manual
Page 48: Zr060 (5 ton belt drive) bottom duct

251933-YTG-J-1009
48
Johnson Controls Unitary Products
ZR036-060 Bottom Duct Application
ZR036 (3 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
800
613
0.35
724
0.40
826
0.46
920
0.53
1007
0.60
1089
0.67
1165
0.75
1237
0.83
1306
0.91
1372
1.00
1000
640
0.40
751
0.46
853
0.52
947
0.58
1034
0.65
1116
0.73
1192
0.80
1264
0.89
1333
0.97
1399
1.05
1200
669
0.48
779
0.53
881
0.59
975
0.65
1063
0.73
1144
0.80
1220
0.88
1293
0.96
1361
1.04
1427
1.13
1400
702
0.57
812
0.63
914
0.69
1009
0.75
1096
0.82
1177
0.90
1254
0.98
1326
1.06
1394
1.14
1460
1.22
1600
741
0.70
852
0.75
954
0.81
1048
0.88
1135
0.95
1217
1.02
1293
1.10
1365
1.18
1434
1.26
1500
1.35
Field Supplied Drive
ZR048 (4 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1000
688
0.40
779
0.47
866
0.55
949
0.63
1029
0.71
1107
0.80
1181
0.88
1253
0.97
1322
1.07
1388
1.16
1200
722
0.45
812
0.53
899
0.60
983
0.68
1063
0.76
1140
0.85
1215
0.93
1286
1.03
1355
1.12
1422
1.21
1400
761
0.53
852
0.60
939
0.68
1022
0.76
1103
0.84
1180
0.92
1254
1.01
1326
1.10
1395
1.20
1462
1.29
1600
807
0.65
897
0.72
984
0.79
1068
0.87
1148
0.95
1225
1.04
1300
1.13
1371
1.22
1440
1.31
1507
1.40
1800
856
0.80
947
0.87
1034
0.95
1118
1.02
1198
1.11
1275
1.19
1349
1.28
1421
1.37
1490
1.46
1557
1.56
2000
910
0.99
1001
1.06
1088
1.14
1172
1.22
1252
1.30
1329
1.39
1403
1.47
1475
1.56
1544
1.66
1611
1.75
Field Supplied Drive
ZR060 (5 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1200
722
0.45
812
0.53
899
0.60
983
0.68
1063
0.76
1140
0.85
1215
0.93
1286
1.03
1355
1.12
1422
1.21
1400
761
0.53
852
0.60
939
0.68
1022
0.76
1103
0.84
1180
0.92
1254
1.01
1326
1.10
1395
1.20
1462
1.29
1600
807
0.65
897
0.72
984
0.79
1068
0.87
1148
0.95
1225
1.04
1300
1.13
1371
1.22
1440
1.31
1507
1.40
1800
856
0.80
947
0.87
1034
0.95
1118
1.02
1198
1.11
1275
1.19
1349
1.28
1421
1.37
1490
1.46
1557
1.56
2000
910
0.99
1001
1.06
1088
1.14
1172
1.22
1252
1.30
1329
1.39
1403
1.47
1475
1.56
1544
1.66
1611
1.75
2200
968
1.23
1059
1.30
1146
1.37
1229
1.45
1309
1.53
1387
1.62
1461
1.71
1533
1.80
1602
1.89
1668
1.99
2400
1029
1.50
1119
1.57
1206
1.65
1290
1.72
1370
1.81
1448
1.89
1522
1.98
1593
2.07
1663
2.16
1729
2.26
2600
1093
1.81
1183
1.88
1270
1.95
1354
2.03
1434
2.11
1511
2.20
1586
2.29
-
-
-
-
-
-
Field Supplied Drive